CONTROL 

 

 
 

Ver. 4.01 

www.profort.com  

Pg. 

3

 

 

                                    Set-up with text message     

1234 = password, 0 = zero, space counts as a character and is therefore important. Do not fill in password if 
PIN is disabled on SIM-card. 

Define the unit 
phone number and 
change password, if 
necessary 

1234 N0 88888888 yyyy 
ID-TEXT 

(N0 = N + zero)

 

1234 = current password, N0, 88888888=mobile 
number of the unit.  

Alternately yyyy=new four-digit password. 

Alternately ID-text: First text in all messages from 
the unit (max. 32 characters). 

Receivers  

 

 

Add    

1234 N1 11111111  

Adds receiver 11111111 in space no. 1 to receive 
alarm as text message. yy yy yy yy 

 

1234 N2 11111111 #  

Adds receiver 11111111 in space no. 2 to receive 
alarm as telephone call with tones. 

Additional spaces (25 total): 

N2..N9, NA (10), NB (11) .. NP (25),. 

Delete   

1234 N1   

Deletes receiver in space no. 1 

Text on input 

Add  

 

1234 A0 BREAK TEXT 

 

TEXT on input 0 by open/break. (A0..A7) 
 

1234 L0 END TEXT 

TEXT on input 0 by close/make. (L0..L7) 

Delete   

1234 A0 
 

Deletes TEXT for input 0 by open/break.  

(A0..A7) 

1234 L0 

Deletes TEXT for input 0 by close/make. (L0..L2) 

Only alarm if text 
is added 

1234 CT

  

The unit ignores input that has no text attached. 

Add analog input 1 
(V1) and 2 (V2) 

1234 V1 S yyyy zzzz 

Set-up of the scale (yyyy = zzzz): (V1 .. V2)  
0-10 V (DIP-switch 1=ON) 

0 10

 

0-20 mA. (DIP-switch 2=ON) 

0 20

 

4-20 mA. (DIP-switch 2=ON) 

-5 20

 

PT100. (DIP-switch 3=ON) 

-309 115

 

Profort PTC. (DIP-switch 4=ON) 

-132 63

 

Add 2: Alarm 
points 

1234 V1 M 5 30 

The unit sends alarm e.g. when temperature 
passes 5 and 30 degrees C.  

 

Add text in LOW 
interval 

1234 V1 A LOW TEMP 

Alarm text in LOW interval (below 5 degrees 
C.) 

Add text in 
MEDÌUM interval 

1234 V1 L NORMAL TEMP 

Alarm text in MEDIUM interval (between 5 and 
30 degrees C.)

 

Summary of Contents for MultiGuard

Page 1: ...ble 230V 12 24V AC DC If necessary a rechargeable 9V battery 3 Turn on the power A diode is lit After approx 20 sec the diode flashes approx every 2 sec and the unit is ready multiGuard DIN9 interior...

Page 2: ...C program on a computer with Windows Download the program from www profort com Start the program and enter the product key specified on the webpage 3 Enter the number on the COM port that the PC uses...

Page 3: ...A 10 NB 11 NP 25 Delete 1234 N1 Deletes receiver in space no 1 Text on input Add 1234 A0 BREAK TEXT TEXT on input 0 by open break A0 A7 1234 L0 END TEXT TEXT on input 0 by close make L0 L7 Delete 1234...

Page 4: ...of alarm 1234 G0 Output is not activated in case of alarm G null Add macro 0 for return of temperature 1234 M0 TEMP V1 R The unit returns value on analogue 1 e g temperature when a text message with t...

Page 5: ...PRS traffic starts 1234 EH GPRS traffic stops Additional control The unit can also be controlled by use of the PC program and all functions can be controlled directly on the Internet On the print ther...

Page 6: ...nd different voice messages by break and close or command 1234 W2 is selected point 6 7 is performed twice First record message for break 3 secs await tone record message for close 3 secs In case of i...

Page 7: ...AC Max 6 A at 35V DC 10VDC output supply Max 100 mA Inputs digital Max 1V 2 mA GND Min 18V max 30 V 24V DC Inputs analog 0 10V DC 0 4 24mA PT 100 Profort temperature sensor 007995 Serial connections R...

Page 8: ...24 V power supply 9 V rechargeable back up battery acquisition Modbus interface IP 65 box Touch display for set up and programming multiGuard Remote IO 1 relay output 2 senders of infrared codes for h...

Reviews: