background image

Gas  

Valve

Yellow

White

Blue

White

Motor

Black

White

Red

White

Yellow

Green

Black

White

Line

Neut
Valve

Ground

Line Cord

Ground

PCB Assembly

High Limit 
Switch

on / off

Thermostat

Spark Plug

Black

Back 

Pressure 

Switch

Green

Black

Orange

White

8

ProFitter

TM

 Operating Instructions and Parts Manual

RMC-FA300PF

If any original wiring as supplied with the heater must be 

replaced, it must be replaced with type AWG105°C wire or its 

equivalent except as indicated (

Type SF2-200, 

∗∗

SGI-250°C) 

Figure 8 – Wiring Diagram

NEVER LEAVE THE HEATER

UNATTENDED WHILE BURNING!

E

N
G

L

I

S

H

ProFitter

TM

Propane Construction Heater

For Technical Support or Troubleshooting, Call: 1-877-447-4768, 8:30 am - 4:30 pm CST         www.ghpgroupinc.com

Wiring Diagram

Summary of Contents for RMC-FA300PF

Page 1: ...OPERTY LOSS OR DAMAGE FROM THE HZARARDS OF FIRE EXPLOSION BURN ASPHYXIATION CARBON MONOXIDE POISONING AND OR ELECTRIC SHOCK ONLY PERSONS WHO CAN UNDERSTAND AND FOLLOW THE INSTRUCTIONS SHOULD USE OR SERVICE THIS HEATER IF YOU NEED ASSISTANCE OR HEATER INFORMATION SUCH AS AN INSTRUCTION MANUAL LABELS ETCETERA CONTACT THE MANUFACTURER General Safety Information IMPORTANT Be sure to read and understan...

Page 2: ...ces a small amount of carbon monoxide Humans can tolerate small amounts of carbon monoxide for short periods Carbon monoxide can build up in a heated space and failure to provide adequate ventilation could result in poisoning or death For either indoor or outdoor use Adequate ventilation shall be provided in accordance with OSHA 29 CFR 1926 154 Safety Requirements for Temporary and Portable Space ...

Page 3: ... SAFETY CONTROL SYSTEM This system shuts the heater down if the flame is extinguished The fan and motor will continue to operate butthere will not be any heat PROPANE SUPPLY All propane gas and tanks are to be provided by the user This heater should only be used with a tank that has a vapor withdrawal system Refer to the Standard of Storage and Handling of Liquefied Petroleum Gas ANSI NFPA 58 Chap...

Page 4: ...ns Correct all leaks immediately 7 Close propane supply valve Ventilation Always follow the minimum fresh air ventilation requirements If these guidelines are not followed carbon monoxide poisoning can occur Always provide proper amounts of fresh air before operating this heater Provide at least three square feet 0 28 m of fresh outside air for each 100 000 BTU Hr of rating This heater requires a ...

Page 5: ... and Ontario Workplaces Reg 833 25 ppm 5000 ppm 3 ppm Reg 833 Canada STEL 15 minutes Reg 833 1 hour WSBC WorkSafe BC OHS Guidelines Part 5 1 and Ontario Workplaces Reg 833 100 ppm 15000 ppm WSBC 30000 ppm Reg 833 1 0 ppm WorkSafeBC 5 0 ppm Reg 833 Ensure that the flow of combustion and ventilation air exchange cannot become obstructed As the building tightens up during the construction phases vent...

Page 6: ...eset and you can try to light the heater once again TO SHUT DOWN HEATER 1 Tightly close control valve on propane tank s 2 Give the heater a few seconds to burn the gas still left in the hose 3 Turn on off switch to the OFF position 4 Unplug extension cord from power source TO RESTART HEATER NOTE If the safety control stops the flow of gas to the heater the motor will continue to run To restart the...

Page 7: ...ft replace fan as shown in Figure 7 Tighten setscrew firmly be careful not to overtighten 10 Reconnect lead wires as shown in the Wiring Diagram Figure 8 11 Reassemble base fan guard and base lower IGNITOR The only maintenance necessary for the ignitor is to be sure that the gap between the electrodes is kept between 10 and 15 2 5 3 8 mm The ignitor is accessible through the combustion chamber Sto...

Page 8: ...ing Instructions and Parts Manual RMC FA300PF If any original wiring as supplied with the heater must be replaced it must be replaced with type AWG105 C wire or its equivalent except as indicated Type SF2 200 SGI 250 C Figure 8 Wiring Diagram NEVER LEAVE THE HEATER UNATTENDED WHILE BURNING E N G L I S H ProFitterTM Propane Construction Heater For Technical Support or Troubleshooting Call 1 877 447...

Page 9: ...Notes ProFitterTM Operating Instructions and Parts Manual RMC FA300PF NEVER LEAVE THE HEATER UNATTENDED WHILE BURNING For Technical Support or Troubleshooting Call 1 877 447 4768 8 30 am 4 30 pm CST www ghpgroupinc com ...

Page 10: ...55 56 57 58 24 23 22 12 20 14 13 15 16 17 18 19 21 7 9 10 11 8 26 For Technical Support or Troubleshooting Call 1 877 447 4768 ProFitterTM Dyna GloTM Operating Instructions and Parts Manual 10 ProFitterTM Operating Instructions and Parts Manual RMC FA300PF NEVER LEAVE THE HEATER UNATTENDED WHILE BURNING For Repair Parts call 1 877 447 4768 Please provide following information Model number Serial n...

Page 11: ...01633 1 34 Power Cord Assembly 2201163 1 35 Switch 2201549 1 36 Solenoid Valve 2315449 1 37 Screw 2001206 2 38 Connector Inlet 2315595 1 39 Fitting 2315596 1 40 Solenoid Valve Bracket 2315594 1 41 Screw 2000416 2 42 Nut 2000384 2 43 Back Pressure Switch 2201594 1 44 Base Lower 2315589 1 45 Screw 2001355 6 46 PCB Assembly 2201181 1 47 Screw 2001445 2 48 Nut 2000231 2 49 Base 2315588 1 50 Plastic Tu...

Page 12: ...r cord and extension cord for cuts and breaks 2 Be sure that housing is not damaged Make sure there are no obstructions to the fan 3 Straighten blade s to match others 4 Replace motor 1 Check igniter wire Reattach or tighten if loose Check spark module Replace if necessary Check all electrical components 2 Set gap to 0 08 2 mm 3 Replace spark plug 1 If the heaters output is restricted internal tem...

Page 13: ...how long an implied warranty lasts so the above limitation may not apply to you Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you CLAIMS HANDLED AS FOLLOWS 1 Contact your retailer and explain the problem 2 If the retailer is unable to resolve the problem contact ourCustomer Service Dept detailing th...

Page 14: ...s SAVE THIS CARD Place Postage Stamp Here GHP Group Inc 8280 Austin Avenue Morton Grove IL 60053 3207 GHP Group Inc 8280 Austin Ave Morton Grove IL 60053 3207 Tel 877 447 4768 www ghpgroupinc com 8280 Austin Avenue Morton Grove IL 6 0 0 5 3 3 2 0 7 Tel 847 324 5900 Fax 847 324 5901 Toll Free 877 GHP Group 8 7 7 4 4 7 4 7 6 8 www ghpgroupinc com GHP GHP Group Inc 6440 W Howard St Niles IL 60714 330...

Reviews: