background image

3

Model RMC-FA300PF

ProFitter

TM

 Operating Instructions and Parts Manual

• The electrical connection & grounding 
must comply with National Electrical 
Code. ANSI/NFPA 70 or in Canada CSA 
C22.1, Canadian Electrical Code, Part 1. 
Use only a properly grounded three (3) 
prong receptacle.
• Do not restrict inlet or outlet by any 
means. The flow of combustion and 
ventilation air is not to be obstructed.
• This heater should not be directed 
toward any propane-gas container 
within 20 ft (6 m). The heater must be 
located at least 6 ft. (1.83 m) in the U.S.; 
or (ii) 10 ft. (3 m) in Canada, from any 
propane gas container.
• The propane cylinder supply system 
must be arranged to provide for vapour 
withdrawal from the operating cylinder.
• This heater is not to be used with 
external thermostats, timers or other 
devices that control or alter electrical 
supply to the heater.
•  Installation of this Appliance at 

altitudes above 2000 ft. (610 m) shall be 

in accordance with local codes, or

in the absence of local codes the, 

National Fuel Gas Code, ANSI Z223.1 / 

NFPA 54, or National Standard of

Canada, Natural Gas and Propane 

Installation Code, CSA B149.1. 

Motor and fan must be 
running before lighting, 

during operation and at shutdown, in order 
to prevent a flame-out condition which could 
result in personal injury or property 
damage.

• Do not adjust regulator below 7 PSIG 
or above 10 PSIG

Theory of Operation

FUEL SYSTEM

The hose/regulator assembly runs from 
the propane supply to the heater itself. 
After the gas runs through the hose  
and regulator, it passes through the 
solenoid valve and out the nozzle into 
the combustion chamber.

AIR SYSTEM

The internal motor turns the fan, which 
pushes air around and through the 
combustion chamber. Here the air is 
heated and provides a constant stream 
of warmth.

IGNITION SYSTEM

The spark module sends voltage to the 
ignitor. The ignitor ignites the fuel and 
air mixture.

SAFETY CONTROL SYSTEM

This system shuts the heater down 
if the flame is extinguished. The fan 

and motor will continue to operate, 
butthere will not be any heat.

PROPANE SUPPLY

All propane gas and tanks are to be 
provided by the user.
This heater should only be used with  
a tank that has a vapor withdrawal 
system. Refer to the Standard of 
Storage and Handling of Liquefied 
Petroleum Gas, ANSI/NFPA 58, Chapter 
5. Your local fire department or library 
will have this information.
Two factors will dictate how much 
propane is used from each tank:
1. The amount of gas in each tank.
2. The surrounding air temperature at 

each tank.

The chart below shows how many tanks 
should be used at a given tempera ture. 
This heater should not be operated with 
a tank smaller than 100 pounds.

Average 

Temperature   

at Tank Location

40

 32

 20

 10

 0

 -10

 -20

 

Number  

of Tanks

3

Use larger tank

Use larger tank

Use larger tank

Use larger tank

Use larger tank

Use larger tank

Use larger tank

°F

40

32

20

10

0

-10

-20

°C

4.44

0

-6.67

-12.22

-17.78

-23.33

-28.89

As the tempera ture drops, less gas is 
vaporized, so a larger tank may be 
necessary in very cold weather. Never 
operate this heater with a tank smaller 
than 100 pounds. Your local propane 
dealer can help you select the proper 
tank size and configuration. 

VENTILATION

For either indoor or outdoor use. 
Adequate ventilation shall be provided 
in accordance with OSHA 29 CFR
1926.154, Safety Requirements for 
Temporary and Portable Space Heating 
Devices and Equipment ANSI A10.10, 
ANSI 223.1 / NFPA 54, Liquified 
Petroleum Gas Code, NFPA 58 or the 
National Gas and Propane Installation 
Code, CAN B149.1 as appropriate.

Ignitor

Fan

Motor

Cool Air In (Back)

Clean Heated 

Air Out (Front)

Combustion Chamber

Air For Heating

Air For Combustion

PCB Control

Nozzle Solenoid Valve

Spark Module (Spark Ignitor)

Hose / Regulator 

Assembly

On/Off Switch

Power Cord

Figure 2 – Cross Section Operational View

NEVER LEAVE THE HEATER

UNATTENDED WHILE BURNING!

E

N
G

L

I

S

H

RMC-FA300PF

For Technical Support or Troubleshooting, Call: 1-877-447-4768, 8:30 am - 4:30 pm CST         www.ghpgroupinc.com

Summary of Contents for RMC-FA300PF

Page 1: ...OPERTY LOSS OR DAMAGE FROM THE HZARARDS OF FIRE EXPLOSION BURN ASPHYXIATION CARBON MONOXIDE POISONING AND OR ELECTRIC SHOCK ONLY PERSONS WHO CAN UNDERSTAND AND FOLLOW THE INSTRUCTIONS SHOULD USE OR SERVICE THIS HEATER IF YOU NEED ASSISTANCE OR HEATER INFORMATION SUCH AS AN INSTRUCTION MANUAL LABELS ETCETERA CONTACT THE MANUFACTURER General Safety Information IMPORTANT Be sure to read and understan...

Page 2: ...ces a small amount of carbon monoxide Humans can tolerate small amounts of carbon monoxide for short periods Carbon monoxide can build up in a heated space and failure to provide adequate ventilation could result in poisoning or death For either indoor or outdoor use Adequate ventilation shall be provided in accordance with OSHA 29 CFR 1926 154 Safety Requirements for Temporary and Portable Space ...

Page 3: ... SAFETY CONTROL SYSTEM This system shuts the heater down if the flame is extinguished The fan and motor will continue to operate butthere will not be any heat PROPANE SUPPLY All propane gas and tanks are to be provided by the user This heater should only be used with a tank that has a vapor withdrawal system Refer to the Standard of Storage and Handling of Liquefied Petroleum Gas ANSI NFPA 58 Chap...

Page 4: ...ns Correct all leaks immediately 7 Close propane supply valve Ventilation Always follow the minimum fresh air ventilation requirements If these guidelines are not followed carbon monoxide poisoning can occur Always provide proper amounts of fresh air before operating this heater Provide at least three square feet 0 28 m of fresh outside air for each 100 000 BTU Hr of rating This heater requires a ...

Page 5: ... and Ontario Workplaces Reg 833 25 ppm 5000 ppm 3 ppm Reg 833 Canada STEL 15 minutes Reg 833 1 hour WSBC WorkSafe BC OHS Guidelines Part 5 1 and Ontario Workplaces Reg 833 100 ppm 15000 ppm WSBC 30000 ppm Reg 833 1 0 ppm WorkSafeBC 5 0 ppm Reg 833 Ensure that the flow of combustion and ventilation air exchange cannot become obstructed As the building tightens up during the construction phases vent...

Page 6: ...eset and you can try to light the heater once again TO SHUT DOWN HEATER 1 Tightly close control valve on propane tank s 2 Give the heater a few seconds to burn the gas still left in the hose 3 Turn on off switch to the OFF position 4 Unplug extension cord from power source TO RESTART HEATER NOTE If the safety control stops the flow of gas to the heater the motor will continue to run To restart the...

Page 7: ...ft replace fan as shown in Figure 7 Tighten setscrew firmly be careful not to overtighten 10 Reconnect lead wires as shown in the Wiring Diagram Figure 8 11 Reassemble base fan guard and base lower IGNITOR The only maintenance necessary for the ignitor is to be sure that the gap between the electrodes is kept between 10 and 15 2 5 3 8 mm The ignitor is accessible through the combustion chamber Sto...

Page 8: ...ing Instructions and Parts Manual RMC FA300PF If any original wiring as supplied with the heater must be replaced it must be replaced with type AWG105 C wire or its equivalent except as indicated Type SF2 200 SGI 250 C Figure 8 Wiring Diagram NEVER LEAVE THE HEATER UNATTENDED WHILE BURNING E N G L I S H ProFitterTM Propane Construction Heater For Technical Support or Troubleshooting Call 1 877 447...

Page 9: ...Notes ProFitterTM Operating Instructions and Parts Manual RMC FA300PF NEVER LEAVE THE HEATER UNATTENDED WHILE BURNING For Technical Support or Troubleshooting Call 1 877 447 4768 8 30 am 4 30 pm CST www ghpgroupinc com ...

Page 10: ...55 56 57 58 24 23 22 12 20 14 13 15 16 17 18 19 21 7 9 10 11 8 26 For Technical Support or Troubleshooting Call 1 877 447 4768 ProFitterTM Dyna GloTM Operating Instructions and Parts Manual 10 ProFitterTM Operating Instructions and Parts Manual RMC FA300PF NEVER LEAVE THE HEATER UNATTENDED WHILE BURNING For Repair Parts call 1 877 447 4768 Please provide following information Model number Serial n...

Page 11: ...01633 1 34 Power Cord Assembly 2201163 1 35 Switch 2201549 1 36 Solenoid Valve 2315449 1 37 Screw 2001206 2 38 Connector Inlet 2315595 1 39 Fitting 2315596 1 40 Solenoid Valve Bracket 2315594 1 41 Screw 2000416 2 42 Nut 2000384 2 43 Back Pressure Switch 2201594 1 44 Base Lower 2315589 1 45 Screw 2001355 6 46 PCB Assembly 2201181 1 47 Screw 2001445 2 48 Nut 2000231 2 49 Base 2315588 1 50 Plastic Tu...

Page 12: ...r cord and extension cord for cuts and breaks 2 Be sure that housing is not damaged Make sure there are no obstructions to the fan 3 Straighten blade s to match others 4 Replace motor 1 Check igniter wire Reattach or tighten if loose Check spark module Replace if necessary Check all electrical components 2 Set gap to 0 08 2 mm 3 Replace spark plug 1 If the heaters output is restricted internal tem...

Page 13: ...how long an implied warranty lasts so the above limitation may not apply to you Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you CLAIMS HANDLED AS FOLLOWS 1 Contact your retailer and explain the problem 2 If the retailer is unable to resolve the problem contact ourCustomer Service Dept detailing th...

Page 14: ...s SAVE THIS CARD Place Postage Stamp Here GHP Group Inc 8280 Austin Avenue Morton Grove IL 60053 3207 GHP Group Inc 8280 Austin Ave Morton Grove IL 60053 3207 Tel 877 447 4768 www ghpgroupinc com 8280 Austin Avenue Morton Grove IL 6 0 0 5 3 3 2 0 7 Tel 847 324 5900 Fax 847 324 5901 Toll Free 877 GHP Group 8 7 7 4 4 7 4 7 6 8 www ghpgroupinc com GHP GHP Group Inc 6440 W Howard St Niles IL 60714 330...

Reviews: