Note 4: The maximum number depends on the selected Fan Speed Mode. E.g if 3-speed is selected,
then the range is 1..4 (corresponding speeds 0..3).
Note 5: By setting BO9 on, the setpoint is reset continuously preventing the user adjustment.
Device Object Properties
App_Config Object
NOTE: Application Configuration Object exposes the configuration parameters over the
BACnet. However please check if your BACnet client can support ProTRIetary Object types to
be able to access these parameters. Alternatively set the configuration parameters through
the SRT touchscreen.
Property Name /ID
Attributes
Range
Default
Object Identifier
R/W
20
Object Name
R/W
32 Characters Max
Concatenation of product type and MAC
address i.e. "TRI_001"
Object Type
R
Device
System Status
R
STATUS_OPERATIONAL
Vendor Name
R
Produal Oy
Vendor Identifier
783
Model Name
R
TRI7
Protocol Version
R
1
Protocol Revision
R
10
Max APDU Length
R
480
Segmentation Support
R
No
APDU Timeout
R
6000 ms
Number APDu Retries
R
3
MaxMaster
R
127
Max_Info_Frames
R
1
Database Revision
R
0
Property Name /ID
Attributes
Range
Default
Required
Object
Properties
Object Identifier
R
proTRIetary-128
Object Name
R/W
"App_Config"
Object Type
R
proTRIetary-128
Optional
Properties
None
Property ID
Description
BACnet Data Type
Range
ProTRIetary
Properties
40100
Nominal Setpoint
REAL
0.0...99.9°C/°F (Default 21°C)
40101
Setpoint Unit
Unsigned
0 = Temperature (Default)
1 = Percentage
2 = None (no setpoint)
3 = Temperature Rel. (relative)
4 = State Select
40102
Sensor 3 Source
Unsigned
0 = Buillt-In Sensor (Default)
1 = Network Sensor
40104
Minimum Setpoint
REAL
0.0...99.9°C/°F/% (Default 14°C)
40105
Maximum Setpoint
REAL
0.0...99.9°C/°F/% (Default 30°C)
40107
Sensor 1 Source
Unsigned
0 = RI1
1 = Network Sensor (Default)