BACnet Standard Object
Types Supported
No dynamic Creation or Deletion supported. Objects, and object instances, are assigned to fixed
functions within the proTRIetary control application of the product as follows
Note 1: If the BACnet object state is overriden locally (e.g. OFF/ECO/Lock locally cancelled), then to
read the device status in the Present Value field, set all TRIority inputs to ’null’.
Note 2: Light and AC icons can be locally overridden only if the all priority inputs are set to ’null’.
Note 3: Set to ’5=none’ to allow users to change the Mode through the screen.
Object
Number Of
Instances
Instance Assignments
Device Object
1
Analog Input
6
AI(0) – Sensor 3 (Built-In Sensor)
AI(1) - Setpoint (Calculated)
AI(2) - Humidity Measurement
AI(3) – Sensor 1 (RI1)
AI(4) – Sensor 2 (RI2)
AI(5) – CO2 Measurement
Analogue Value
8
AV(0) - Nominal Setpoint
AV(1) - Sensor 1 Temp
AV(2) - Sensor 2 Temp
AV(3) - Sensor 3 Temp
AV(4) - Brightness
AV(5) - Y1 Output
AV(6) - Y2 Output
AV(7) - Y3 Output
Binary Input
5
BI(0) – Digital Input (DI1)
BI(1) – Boost (Party Mode) Status
BI(2) – Schedule Status (only TRI-P-1R)
BI(3) – Time Lost (only TRI-P-1R)
BI(4) – Auto Fan Status
Binary Output
11
BO(0) – Relay
BO(1) - OFF Status
*1
BO(2) - ECO Status
"1
BO(3) – Lights
*2
BO(4) – AC
*2
BO(5) – Lock
*1
BO(6) – Frost Icon
BO(7) - Non Volatile Update (updates
setpoints/configuration parameters)
BO(8) – Boost Icon
BO(9) – Reset Setpoint (User Adj)
*5
BO(10) – Night Status / Override
MutliState Value
7
MSV(0) - Ring Colour [Read/Write]
(1-White, 2=Red, 3=Blue, 4=Green,
5=Orange, 6=Yellow, 7=Magnenta,
8=Cyan, 9=Sensor1, 10=Sensor2,
11=Sensor3)
MSV(1) - ModeIconOverride
[Read/Write]
(1=Auto, 2=Heating,
3=Cooling, 4=Fan, 5=None)
*3
MSV(2) - FanAutoSpeed [Read/Write]
1..7 (corresponding speeds 0..6)
*4
MSV(3) - Device Mode Status [Read
Only]
(1=Comfort, 3=OFF, 4=Boost)
MSV(4) - Alarm Status [Read Only]
(Add 1 to to bit values)
Bit 0 - Internal NTC (1)
Bit 1 - RI1 (2)
Bit 2 - RI2 (4)
Bit 3 - Humidity Sensor (8)
Bit 4 - DI1 (16)
Bit 5 - DI2 (Not Applicable)
Bit 6 - Time Lost (64)
MSV(5) - Mode Icon Status [Read
Only]
(1=Auto, 2=Heating, 3=Cooling,
4=Fan)
MSV(6) - Fan Speed Status [Read
Only]
1..7 (corresponding speeds 0..6)
*4