Published: 18.07.2019
55 (63)
12.
Select the disconnecting method.
• Select
Disconnect
to disconnect the device without deactivating the device Bluetooth.
• Select
End commissioning
to disconnect the device and deactivate the device Bluetooth.
Note:
The wireless network communication (MIRA communication) starts only if
the Bluetooth is deactivated. However, the device also deactivates the Bluetooth if
connection to Produal MyTool
®
is lost for 30 minutes.
6.1 Configuring user interface
1.
Press the
UI Settings
button in the
Configurations
view.
2.
Make the settings.
See the chapter
Available settings for user interface
on page 55 for more details.
3.
Press the
Confirm changes
button to save the changes.
4.
Press
Install to device
button to write the changes to the device.
6.1.1 Available settings for user interface
Parameter name Values
Default
Description
Display brightness
1...10
5
Display brightness level.
Display mode
Upper value
scrolling, lower
value static / Upper
value static, lower
value scrolling
Upper value
scrolling, lower
value static
Display scrolling settings.
Display static value
Temperature /
Relative humidity /
Measurement
1...4 / External
measurement
1...4 / I2C
measurement
1..3 / VOB value
1..3
Temperature
Static value selection.
Scrolling values to
show
Temperature /
Relative humidity /
Measurement
1...4 / External
measurement
1...4 / I2C
measurement
1..3 / VOB value
1..3
Humidity
Scrolling values selection.
Autoscroll time
1...30 s
10 s
Scrolling value change interval. Time to show each
value on display. Affects also to display off delay.
Display off delay = (number of items in scrolling
value selection) * (display scrolling delay).
Button function
Manual scroll /
Handle button
events on
Gateway / Extra
time function
Manual scroll
Button function. The first press activates the
display if the display is not on.
6.2 Configuring measurement settings
1.
Press the
Measurement Settings
button in the
Configurations
view.
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | [email protected]
Information is subject to change without prior notice.
EN - 5401comm