45 (63)
Note:
The values that are marked with "-" depend on the transmitters' properties.
Regis-
ter
Parameter description
Data type Values
Range
Default
2XX62
Temperature offset.
Signed 16
-500...500
-50,0...50,0 °C
0
2XX63
Humidity offset.
Signed 16
-5000...5000
-50,00...50,00 %rH
0
2XX64
Additional measurement 1 offset
(CO
2
).
-
-
-
0
2XX65
Additional measurement 2 offset.
-
-
-
0
2XX66
Additional measurement 3 offset.
-
-
-
0
2XX67
Additional measurement 4 offset.
-
-
-
0
2XX68
External measurement 1 offset.
-
-
-
0
2XX69
External measurement 2 offset.
-
-
-
0
2XX70
External measurement 3 offset.
-
-
-
0
2XX71
External measurement 4 offset.
-
-
-
0
2XX72
I2C value 1 offset.
-
-
-
0
2XX73
I2C value 2 offset.
-
-
-
0
2XX74
I2C value 3 offset.
-
-
-
0
Holding registers for transmitter output settings
Table reading instruction: The register numbers include an XX in the middle. Replace the XX with the
transmitter ID - 1 value. For example, a transmitter with the ID 6: XX = 05.
Regis-
ter
Parameter description
Data type Values
Range
Default
2XX75
Output 1 mode.
Unsigned 16
0
2XX76
Output 2 mode.
Unsigned 16
0
2XX77
Output 3 mode.
Unsigned 16
0
2XX78
Output 4 mode.
Unsigned 16
0
2XX79
Output 1 overdrive value.
Unsigned 16 0...10000
0...100,00 %
0
2XX80
Output 2 overdrive value.
Unsigned 16 0...10000
0...100,00 %
0
2XX81
Output 3 overdrive value.
Unsigned 16 0...10000
0...100,00 %
0
2XX82
Output 4 overdrive value.
Unsigned 16 0...10000
0...100,00 %
0