background image

 

USER GUIDE 

KRM-X-1 & KRM-X-2 

4 (9) 

 

Produal Oy

 

Keltakalliontie 18, 48770 Kotka FINLAND 

Tel: +358 10 219 9100 / Fax: +358 5 230 9210 

[email protected] 

www.produal.com

 

Information is subject to change without prior notice. 

6.  When installing sensor outdoors or in cold environment, use WDG type housing. Housing prevents 

the warm air in the smoke detector duct from condensing. The interior of the housing is insulated 

with foam rubber. 

 

7.  Attach the housing bottom part (G) with the electronics and sensor to the adapter plate (A). 

The housing (G+F) can be attached at increments of 90°. The direction of the housing has no effect 

on the measurement result. You can align the housing with the sensor optimally. 
The cover screw tightening torque is 1.2 Nm. 

F

G

A

 

 

8.  Wire the unit according to the applicable wiring diagram. 

Power supply

230 Vac

Test/Reset

(NC contact)

9

10
11
12
13
14
15

green

16
17

yellow

blue

Smoke alarm

Smoke alarm
Service signal

Contamination

red

Test/Reset

3
4

Power supply

230 Vac

1
2

          

Power supply

24 Vac/dc

Test/Reset

(NC contact)

9

10
11
12
13
14
15

green

16
17

yellow

blue

Smoke alarm

Smoke alarm
Service signal

Contamination

red

Test/Reset

3
4

Power supply

24 Vac/dc

1
2

5
6
7
8

Bus B

Bus B

Bus A

Bus A

RS485

(for information)

MOD / BAC models

 

                           KRM-X-1 

        KRM-X-2, KRM-X-2-MOD, KRM-X-2-BAC 

  The cable jacket for field wire connecting must be done as near as possible to the terminal 

block. For wires longer than 10 mm, the wire must be fixed by a cable clip near the terminal 

block or insulated in pairs with a suitably protective tube. 

  Test/reset (terminal 9 +10): if bridge circuit is removed, a floating NC contact must be 

connected. 

  The floating switching contacts (terminals 11 – 17) should be assigned as uniformly as possible 

to an installation category according to EN 60730-1. These switching contacts are only to be 

used for 230 Vac or 24 Vac/dc. Combinations are not permitted unless at least one contact 

Summary of Contents for KRM-X-1

Page 1: ...h height or diameter for air ventilation ducts monitored with the 600 mm long standard air collecting tube under the VdS approval DIBt certification The indicated airflow direction must be observed wh...

Page 2: ...es compliance with operating and installation instructions We are not liable for losses due to inappropriate use Unauthorized manipulations or modifications of the device render the operating permit t...

Page 3: ...very for attaching the plate to the duct A 4 When installing on a rectangular air duct fit the plate directly to the tube When installing on a circu lar air duct use KS X fitting plate B and rubber bu...

Page 4: ...2 13 14 15 green 16 17 yellow blue Smoke alarm Smoke alarm Service signal Contamination red Test Reset 3 4 Power supply 230 Vac 1 2 Power supply 24 Vac dc Test Reset NC contact 9 10 11 12 13 14 15 gre...

Page 5: ...simultaneously pressing of T3 and T4 The value is saved when two underscores appear on the display _ _ NOTE The current value is also saved after 6 seconds without a button being pressed TESTING THE S...

Page 6: ...detector processor failure Failure B and alarm A lights light up at the same time Troubleshooting change the detector and confirm by pressing the alarm reset button C all lights on the circuit board...

Page 7: ...mber must have been cleared and fault rectified MAINTENANCE AND REPAIR The smoke detector must be tested at least once a year in order to ensure that it performs reliably over long time periods Withou...

Page 8: ...ner housing Check all seals 6 Assemble all parts The cover screw tightening torque is 1 2 Nm 7 Test system by triggering the smoke detector with test spray 9 14 8 Check with the operator about the fun...

Page 9: ...air flow 4 NTC temperature value The value can be used to determine the ambient temperature The value is combination of the ambient temperature and self heating of the circuit board See the following...

Reviews: