Procom SSU320RHL-B Owner'S Operation And Installation Manual Download Page 8

 8

Minimum Wall and Ceiling Clearances

(see Figure 4)
A. Clearances from outermost point of

stove top to any combustible side
wall  should  not  be  less  than  12
inches.

B. Clearances from outermost point

of  stove  top  to  any  combustible
back wall should not  be less than
6   i n c h e s   ( l n c l u d e s   c o r n e r
installations).

C. Clearances from the stove top to the

ceiling should not be less than 48
inches.

CONNECTING TO GAS
SUPPLY

INSTALLATION  ITEMS NEEDED

Before installing heater, make sure you  have the items listed
below.

piping (check local codes)

l

    sealant (resistant to propane/LP gas)

l

    equipment shutoff  valve*

l

    test gauge connection*

l

    sediment trap

l

    tee joint

l

    pipe wrench

l

    flexible gas hose. (Check local codes)

*A CSA design-certified equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge  connection.
Purchase  the optional  CSA  design-certified equipment
shutoff  valve from your dealer.

The installer must supply an external regulator. The external
regulator will reduce incoming gas pressure. If you do not
reduce incoming gas pressure, heater regulator damage could
occur. lnstall external regulator with the vent  pointing down as
shown in Figure 6. Pointing the vent down protects it from
freezing rain or sleet.

Figure  5 - Gas Regulator Location For Gas inlet Connection

  

WARNING:

  

A qualified service

person must connect heater to gas
supply. Follow all local codes.

  

WARNING:  

This appliance re-

quires  a  3/8"  NPT  (National  Pipe
Thread) inlet connection to the pres-
sure regulator.

 

WARNING:

   Never connect heater

to private (non-utility) gas wells. This
gas is commonly known as wellhead
gas.

 

WARNING: 

Do not over tighten

gas connections

  

CAUTION:

   Never connect heater

directly to the gas supply. This heater
requires an external regulator (not
supplied). lnstall the external regu-
lator between the  heater and  gas
supply.

  

CAUTION:

   Use only new, black iron or steel pipe.

Internally-tinned copper tubing may be used in certain
areas. Check your local codes. Use pipe of 1/2" diameter
or greater to allow proper gas volume to heater. If pipe is
too small, undue loss of pressure will occur.

  

CAUTION:

   Avoid damage to regulator. Hold gas regu-

lator with wrench when connecting into gas piping and/or
fittings.

  

CAUTION:

   Use pipe joint sealant that is resistant to

gas (PROPANE or NG).

INSTALLATION

Continued

Summary of Contents for SSU320RHL-B

Page 1: ...tion An unvented room heater produces approximately one 1 ounce 30 ml of water for every 1 000BTU S 3KW S OF gas input per hour Refer to page 7 Installer Please leave these instructions with the consu...

Page 2: ...rns Ceiling fans can create drafts that al ter burner flame patterns Altered burner patterns can cause sooting WARNING Any change to this fireplace or its controls can be dangerous DANGER Carbon monox...

Page 3: ...r Use only the logs provided with the heater 6 Do not add extra logs or ornaments such as pine cones vermiculite or rock wool Using these added items can cause sooting Do not add lava rock around base...

Page 4: ...l system This system requires no matches or batteries to light heater THERMOSTATIC HEAT CONTROL MODULE This heater has a control module with a thermostat sensing bulb SET TEMP with remote control This...

Page 5: ...ve a Confined or Unconfined Space Use this worksheet to determine if you have a confined or unconfined space Space Includes the room in which you will install heater plus any adjoining rooms with door...

Page 6: ...rea in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction provide adequate combustion and ventilation air by one...

Page 7: ...re See Air for Combus tion and Ventilation pages 5 and 6 NOTICE This heater is intended for use as supplemental heat Use this heater along with your primary heat ing system Do not install this heater...

Page 8: ...oming gas pressure heater regulator damage could occur lnstall external regulator with the vent pointing down as shown in Figure 6 Pointing the vent down protects it from freezing rain or sleet Figure...

Page 9: ...hutoff valve see Figure 8 2 Pressurize supply piping system by either using compressed air or open ing natural supply tank valve 3 Check all joints from gas meter to equipment shutoff valve see Figure...

Page 10: ...7 Insert the recessed hole on the bottom of log 7 onto the pin on log 2 with the other end placed on log 3 It is very important to install the logs exactly as instructed Do not modify logs Only use l...

Page 11: ...ng heater for the first time the ignition period may be 30 seconds or longer This will al low air to exit from the gas system Note The pilot is located on back of front burner If pilot does not stay l...

Page 12: ...L child proof 1 Key press locking Press LOCK button a symbol will appear on the LCD 2 Key press unlocking Press then press LOCK button to unlock OPERATING FAN Press FAN button for desired fan operatio...

Page 13: ...ghting Instructions Figure 16 Manual Control 5 Wait five 5 minutes to clear out any gas Then smell for gas in cluding near the floor If you smell gas STOP Follow B in the safety information on page 11...

Page 14: ...ing season Blocked air holes will create soot We recommend that you clean the unit every three months during opera tion and have heater inspected yearly by a qualified service person DISCONNECT WIRING...

Page 15: ...utes 2 Inspect burner pilot and primary air inlet holes on injector holder for dust and dirt See Figure 23 3 B l o w a i r t h r o u g h t h e ports slots and holes in the burner 4 Check the injector...

Page 16: ...manual When contacting your dealer or PRO COM have ready l Your name l Your address l Model and serial numbers of your heater l How heater was malfunctioning l Type of gas used Propane LP or Natural...

Page 17: ...OFF switch ON 4 Check the wire for damage and make sure connection is tight 5 Replace Pilot 6 Place the control knob of manual override on OFF position for at least 1 minute then turn to ELEC TRIC pos...

Page 18: ...urner inlet blocked 3 Burner flame holes blocked 1 Metal expanding while heating or contracting while cooling 1 Heated vapors from furniture polish wax carpet cleaners etc turn into white powder resid...

Page 19: ...rements Page 5 POSSIBLECAUSE 1 Heater is burning vapors from paint hair spray glues etc See IMPOR TANT statement at beginning of troubleshooting 2 Gas leak See WARNING Statement at beginning of troubl...

Page 20: ...91 05 INJECTOR 1 5 ML091 10 INJECTOR 1 6 ML056 04 CONNECTOR 1 1 7 SLU35A031 OUTLET TUBE 1 1 8 NAY03 05 01 IGNITOR CABLE 1 1 9 AL092 01 IGNITOR 1 1 10 QL027 02 INJECTOR 1 11 QL028 02 INJECTOR 1 12 ND47...

Page 21: ...1 2 SLU35A130 GB DOOR WITH SCREEN 1 SLU35A130 B DOOR WITH SCREEN 1 SLU35A130 G DOOR WITH SCREEN 1 SLU35A130 S DOOR WITH SCREEN 1 3 SLU35A106 GB ACCESS PANEL 1 SLU35A106 B ACCESS PANEL 1 SLU35A106 G AC...

Page 22: ......

Reviews: