Procom SSU320RHL-B Owner'S Operation And Installation Manual Download Page 6

 6

If  the  actual  Btu/Hr  used  is  less  than  the  maximum  Btu/Hr  the  space  can  support,  the  space  is  an
unconfined space. You will need no additional fresh air ventilation.

3. Add the Btu/Hr of all fuel burning appliances in the space.

     Vent-free heater                                                       Btu/Hr
     Gas water heater*                                                    Btu/Hr
     Gas furnace                                                             Btu/Hr
     Vented gas heater                                                   Btu/Hr
     Gas heater logs                                                       Btu/Hr
     Other gas appliances* +                                          Btu/Hr
    Total                                =                                        Btu/Hr

        *Do  not  include  direct-vent  gas  appliances.  Direct-vent  draws  combustion  air  from  the  outdoors  and
       vents to the outdoors.
4. Compare  the  maximum  Btu/Hr  the  space  can  support  with  the  actual amount of Btu/Hr used.

                          

Btu/Hr (maximum the space can support)

                         

Btu/Hr (actual amount of Btu/Hr used)

         

Example

 :  51,200 Btu/Hr(maximum the space can support)

                           56,000 Btu/Hr(actual amount of Btu/Hr used)
The  space  in  the  above  example  is  a  confined  space  because  the  actual  Btu/Hr  used  is  more  than  the
maximum Btu/Hr the space can support.
You must provide additional fresh air.  Your options are as follows:
 A.  Rework worksheet, adding  the space of an adjoining room. If the extra space provides an unconfined space,
remove door to adjoining room or add ventilation grills between rooms. 

See Ventilation Air  From Inside Building

.

B.  Vent room directly to the outdoors. See  

Ventilation Air From Outdoors

 .

C.  Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

Figure  2 -Ventilation Air from Inside Building

 Example:
 Gas  water  heater          30,000        Btu/Hr
 Vent-free  heater    +      26,000        Btu/Hr
 Total                         =     56,000        Btu/Hr

NOTE:  

If  the area in  which the heater may be operated is smaller than that defined as an unconfined space or if  the

building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods
described in the 

National Fuel Gas Code, ANSI Z223.1, Section 5.3

 or applicable local codes.

This fresh air would come from an adjoining unconfined
space. When ventilating to an adjoining unconfined space,
you must provide two permanent openings: one within
12" of the ceiling and one within 12" of the floor on the
wall connecting the two spaces (see options 1 and 2,
Figure 2). You can also remove door into adjoining room
(see option 3, Figure 2). Follow  the 

National Fuel Gas

Code. NFPA 54/ANSI Z223.1, Section 5.3, Air for Com-
bustion and Ventilation

 for required size of ventilation grills

or ducts.

Ventilation Air From lnside Building

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts.
You must provide two permanent openings: one within
12" of the ceiling and one within 12" of the floor. Connect
these items directly to the outdoors or spaces open to
the outdoors. These spaces include attics and crawl
spaces. Follow the 

National Fuel Gas Code, NFPA 54/

ANSI Z223.1, Section 5.3, Air for Combustion and Ven-
tilation

 for required size of ventilation grills or ducts.

IMPORTANT:

 Do not provide openings for inlet or outlet

air into attic if attic has a thermostat-controlled power
vent. Heated air entering the attic will activate the power
vent.
Rework worksheet, adding the space of the adjoining
unconfined space. The combined spaces must have
enough fresh air to supply all appliances in both spaces.

Figure  3 -Ventilation Air from Outdoors

Summary of Contents for SSU320RHL-B

Page 1: ...tion An unvented room heater produces approximately one 1 ounce 30 ml of water for every 1 000BTU S 3KW S OF gas input per hour Refer to page 7 Installer Please leave these instructions with the consu...

Page 2: ...rns Ceiling fans can create drafts that al ter burner flame patterns Altered burner patterns can cause sooting WARNING Any change to this fireplace or its controls can be dangerous DANGER Carbon monox...

Page 3: ...r Use only the logs provided with the heater 6 Do not add extra logs or ornaments such as pine cones vermiculite or rock wool Using these added items can cause sooting Do not add lava rock around base...

Page 4: ...l system This system requires no matches or batteries to light heater THERMOSTATIC HEAT CONTROL MODULE This heater has a control module with a thermostat sensing bulb SET TEMP with remote control This...

Page 5: ...ve a Confined or Unconfined Space Use this worksheet to determine if you have a confined or unconfined space Space Includes the room in which you will install heater plus any adjoining rooms with door...

Page 6: ...rea in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction provide adequate combustion and ventilation air by one...

Page 7: ...re See Air for Combus tion and Ventilation pages 5 and 6 NOTICE This heater is intended for use as supplemental heat Use this heater along with your primary heat ing system Do not install this heater...

Page 8: ...oming gas pressure heater regulator damage could occur lnstall external regulator with the vent pointing down as shown in Figure 6 Pointing the vent down protects it from freezing rain or sleet Figure...

Page 9: ...hutoff valve see Figure 8 2 Pressurize supply piping system by either using compressed air or open ing natural supply tank valve 3 Check all joints from gas meter to equipment shutoff valve see Figure...

Page 10: ...7 Insert the recessed hole on the bottom of log 7 onto the pin on log 2 with the other end placed on log 3 It is very important to install the logs exactly as instructed Do not modify logs Only use l...

Page 11: ...ng heater for the first time the ignition period may be 30 seconds or longer This will al low air to exit from the gas system Note The pilot is located on back of front burner If pilot does not stay l...

Page 12: ...L child proof 1 Key press locking Press LOCK button a symbol will appear on the LCD 2 Key press unlocking Press then press LOCK button to unlock OPERATING FAN Press FAN button for desired fan operatio...

Page 13: ...ghting Instructions Figure 16 Manual Control 5 Wait five 5 minutes to clear out any gas Then smell for gas in cluding near the floor If you smell gas STOP Follow B in the safety information on page 11...

Page 14: ...ing season Blocked air holes will create soot We recommend that you clean the unit every three months during opera tion and have heater inspected yearly by a qualified service person DISCONNECT WIRING...

Page 15: ...utes 2 Inspect burner pilot and primary air inlet holes on injector holder for dust and dirt See Figure 23 3 B l o w a i r t h r o u g h t h e ports slots and holes in the burner 4 Check the injector...

Page 16: ...manual When contacting your dealer or PRO COM have ready l Your name l Your address l Model and serial numbers of your heater l How heater was malfunctioning l Type of gas used Propane LP or Natural...

Page 17: ...OFF switch ON 4 Check the wire for damage and make sure connection is tight 5 Replace Pilot 6 Place the control knob of manual override on OFF position for at least 1 minute then turn to ELEC TRIC pos...

Page 18: ...urner inlet blocked 3 Burner flame holes blocked 1 Metal expanding while heating or contracting while cooling 1 Heated vapors from furniture polish wax carpet cleaners etc turn into white powder resid...

Page 19: ...rements Page 5 POSSIBLECAUSE 1 Heater is burning vapors from paint hair spray glues etc See IMPOR TANT statement at beginning of troubleshooting 2 Gas leak See WARNING Statement at beginning of troubl...

Page 20: ...91 05 INJECTOR 1 5 ML091 10 INJECTOR 1 6 ML056 04 CONNECTOR 1 1 7 SLU35A031 OUTLET TUBE 1 1 8 NAY03 05 01 IGNITOR CABLE 1 1 9 AL092 01 IGNITOR 1 1 10 QL027 02 INJECTOR 1 11 QL028 02 INJECTOR 1 12 ND47...

Page 21: ...1 2 SLU35A130 GB DOOR WITH SCREEN 1 SLU35A130 B DOOR WITH SCREEN 1 SLU35A130 G DOOR WITH SCREEN 1 SLU35A130 S DOOR WITH SCREEN 1 3 SLU35A106 GB ACCESS PANEL 1 SLU35A106 B ACCESS PANEL 1 SLU35A106 G AC...

Page 22: ......

Reviews: