Procom SSU320RHL-B Owner'S Operation And Installation Manual Download Page 15

1 5

Figure 24 - Pilot Air Inlet Hole

Figure 23 - Burner Primary Air

Inlet

MAIN BURNER

Periodically inspect all burner flame holes
with the heater running. All slotted burner
flame holes should be open with yellow
flame present. All  round burner flame
holes should be open with a small blue
flame present. Some burner flame holes
may become blocked by debris or rust,
with no flame present. If so, turn off heater
and let cool. Either remove blockage or
replace burner.  Blocked  burner  flame
holes will create soot.

We recommend you keep the burner
and pilot assembly clean and free of
dust and dirt.
To clean these parts we recommend
using compressed air no greater than
30 PSI. Your local computer store,
hardware store, or home
center may carry compressed air in a
can. You can use a vacuum cleaner in
the  blow  position.  If  using  com-
pressed air in a can, please follow the
directions on the can. If you don't fol-
low directions on the can, you could
damage the pilot assembly.
1.   Shut off the unit, including the

pilot. Allow  the  unit  to  cool  for
at least thirty minutes.

2 .   I n s p e c t   b u r n e r ,   p i l o t   a n d

p r i m a r y  a i r   i n l e t   h o l e s   o n
injector holder for dust and dirt
(See Figure 23).

3 .   B l o w   a i r   t h r o u g h   t h e

ports/slots  and  holes  in  the
burner.

4.    C h e c k   t h e   i n j e c t o r   h o l d e r

l o c a t e d   a t   t h e   e n d   o f   t h e
burner  tube  again.  Remove
any large particles of dust, dirt,
lint, or pet hair with a soft cloth
or vacuum cleaner nozzle.

5.    Blow  air  into  the  primary  air

holes on the injector holder.

6.    In  case  any  large  clumps  of

dust  have  now  been  pushed
into  the  burner  repeat  steps  3
and 4.

Clean the pilot assembly also. A yel-
low tip on the pilot flame indicates dust
and dirt in the pilot assembly. There
is  a  small  air  inlet  hole  about  two
inches  from  where  the  pilot  flame
comes out of the pilot assembly (see
Figure 24). With the unit off, lightly blow
air through the air inlet hole. You may
blow through a drinking straw if com-
pressed air is not available.

Figure 25 - Override Control System Diagram

CABINET

Air Passageways

l

  

Use a vacuum cleaner or pressur-

ized air to clean.

Exterior

l

 

 Use a soft cloth dampened with a

mild soap and water mixture. Wipe
the cabinet to remove dust.

Logs

l

 

 If you remove logs for cleaning, re-

fer to Installing Logs to properly re-
place logs.

l

 

 Replace logs if broken or chipped

(dime size or larger).

Summary of Contents for SSU320RHL-B

Page 1: ...tion An unvented room heater produces approximately one 1 ounce 30 ml of water for every 1 000BTU S 3KW S OF gas input per hour Refer to page 7 Installer Please leave these instructions with the consu...

Page 2: ...rns Ceiling fans can create drafts that al ter burner flame patterns Altered burner patterns can cause sooting WARNING Any change to this fireplace or its controls can be dangerous DANGER Carbon monox...

Page 3: ...r Use only the logs provided with the heater 6 Do not add extra logs or ornaments such as pine cones vermiculite or rock wool Using these added items can cause sooting Do not add lava rock around base...

Page 4: ...l system This system requires no matches or batteries to light heater THERMOSTATIC HEAT CONTROL MODULE This heater has a control module with a thermostat sensing bulb SET TEMP with remote control This...

Page 5: ...ve a Confined or Unconfined Space Use this worksheet to determine if you have a confined or unconfined space Space Includes the room in which you will install heater plus any adjoining rooms with door...

Page 6: ...rea in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction provide adequate combustion and ventilation air by one...

Page 7: ...re See Air for Combus tion and Ventilation pages 5 and 6 NOTICE This heater is intended for use as supplemental heat Use this heater along with your primary heat ing system Do not install this heater...

Page 8: ...oming gas pressure heater regulator damage could occur lnstall external regulator with the vent pointing down as shown in Figure 6 Pointing the vent down protects it from freezing rain or sleet Figure...

Page 9: ...hutoff valve see Figure 8 2 Pressurize supply piping system by either using compressed air or open ing natural supply tank valve 3 Check all joints from gas meter to equipment shutoff valve see Figure...

Page 10: ...7 Insert the recessed hole on the bottom of log 7 onto the pin on log 2 with the other end placed on log 3 It is very important to install the logs exactly as instructed Do not modify logs Only use l...

Page 11: ...ng heater for the first time the ignition period may be 30 seconds or longer This will al low air to exit from the gas system Note The pilot is located on back of front burner If pilot does not stay l...

Page 12: ...L child proof 1 Key press locking Press LOCK button a symbol will appear on the LCD 2 Key press unlocking Press then press LOCK button to unlock OPERATING FAN Press FAN button for desired fan operatio...

Page 13: ...ghting Instructions Figure 16 Manual Control 5 Wait five 5 minutes to clear out any gas Then smell for gas in cluding near the floor If you smell gas STOP Follow B in the safety information on page 11...

Page 14: ...ing season Blocked air holes will create soot We recommend that you clean the unit every three months during opera tion and have heater inspected yearly by a qualified service person DISCONNECT WIRING...

Page 15: ...utes 2 Inspect burner pilot and primary air inlet holes on injector holder for dust and dirt See Figure 23 3 B l o w a i r t h r o u g h t h e ports slots and holes in the burner 4 Check the injector...

Page 16: ...manual When contacting your dealer or PRO COM have ready l Your name l Your address l Model and serial numbers of your heater l How heater was malfunctioning l Type of gas used Propane LP or Natural...

Page 17: ...OFF switch ON 4 Check the wire for damage and make sure connection is tight 5 Replace Pilot 6 Place the control knob of manual override on OFF position for at least 1 minute then turn to ELEC TRIC pos...

Page 18: ...urner inlet blocked 3 Burner flame holes blocked 1 Metal expanding while heating or contracting while cooling 1 Heated vapors from furniture polish wax carpet cleaners etc turn into white powder resid...

Page 19: ...rements Page 5 POSSIBLECAUSE 1 Heater is burning vapors from paint hair spray glues etc See IMPOR TANT statement at beginning of troubleshooting 2 Gas leak See WARNING Statement at beginning of troubl...

Page 20: ...91 05 INJECTOR 1 5 ML091 10 INJECTOR 1 6 ML056 04 CONNECTOR 1 1 7 SLU35A031 OUTLET TUBE 1 1 8 NAY03 05 01 IGNITOR CABLE 1 1 9 AL092 01 IGNITOR 1 1 10 QL027 02 INJECTOR 1 11 QL028 02 INJECTOR 1 12 ND47...

Page 21: ...1 2 SLU35A130 GB DOOR WITH SCREEN 1 SLU35A130 B DOOR WITH SCREEN 1 SLU35A130 G DOOR WITH SCREEN 1 SLU35A130 S DOOR WITH SCREEN 1 3 SLU35A106 GB ACCESS PANEL 1 SLU35A106 B ACCESS PANEL 1 SLU35A106 G AC...

Page 22: ......

Reviews: