Use this work sheet to determine if you have 

a confined or unconfined space.

Space: 

Includes the room in which you will 

install heater plus any adjoining rooms with 

doorless  passageways  or  ventilation  grills 

between the rooms.
1.  Determine the volume of the space (length 

x width x height).

 

Length  x  Width  x  Height  =__________

 

cu. ft. (volume of space)

 

Example:

  Space  size  20  ft.  (6.1  m) 

(length)  x  16  ft.  (4.88  m)  (width)  x

 

8 ft. (2.44 m) (ceiling height) = 2560 cu. 

ft. (72.49 m

3

) (volume of space)

 

If additional ventilation to adjoining room 

is supplied with grills or openings, add the 

volume of these rooms to the total volume 

of the space.

2.  Multiply the space volume by 20 to deter-

mine the maximum Btu/Hr the space can 

support.

 

  ________(volume  of  space)  x  20  = 

(Maximum Btu/Hr the space can support)

 

Example:

 2560 cu. ft. (72.49 m

3

) (volume 

of space) x 20 = 51,200 (maximum Btu/

Hr the space can support)

3.  Add the Btu/Hr of all fuel burning appli-

ances in the space.

 

Vent-free heater 

 _________ Btu/Hr

 

Gas water heater*   _________ Btu/Hr

 

Gas furnace 

 _________ Btu/Hr

 

Vented gas heater   _________ Btu/Hr

 

Gas fireplace logs   _________ Btu/Hr

 

Other gas appl _______ Btu/Hr

 

Total 

= ________ Btu/Hr

 

*  Do  not  include  direct-vent  gas  appli-

ances.  Direct-vent  draws  combustion 

air  from  the  outdoors  and  vents  to  the 

outdoors.

AIR FOR COMBUSTION AND VENTILATION

 

30,000

  26,000

  56,000

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

 

Example:

 

 

Gas water heater   __________ Btu/Hr

 

Vent-free heater 

+ _________ Btu/Hr

 

Total 

= _________ Btu/Hr

4.  Compare the maximum Btu/Hr the space 

can support with the actual amount of Btu/

Hr used.

 

  _______Btu/Hr (maximum can support)

 

  _______Btu/Hr (actual amount used)

 

Example:

 51,200  Btu/Hr  (maximum  the 

space can support)

 

 

56,000 Btu/Hr (actual amount 

of Btu/Hr used)

The space in the above example is a confined 

space because the actual Btu/Hr used is more 

than the maximum Btu/Hr the space can sup-

port. You  must  provide  additional  fresh  air. 

Your options are as follows:
A.  Rework  worksheet,  adding  the  space 

of an adjoining room. If the extra space 

provides  an  unconfined  space,  remove 

door to adjoining room or add ventilation 

grills between rooms. See 

Ventilation Air 

From Inside Building, 

page 9

.

B.  Vent room directly to the outdoors. See 

Ventilation Air From Outdoors, 

page 9.

C.  Install a lower Btu/Hr heater, if lower Btu/

Hr size makes room unconfined. If the ac-

tual Btu/Hr used is less than the maximum 

Btu/Hr the space can support,

 

the space 

is an unconfined space. You will need no 

additional fresh air ventilation.

Summary of Contents for MN060HBA

Page 1: ...personal injury or loss of life Do not store or use gasoline or other flammable va pors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any...

Page 2: ...tly located manufactured mobile home where not prohibited by local codes This appliance is only for use with propane or natural gas This appliance is equipped with a simple means to switch between pro...

Page 3: ...e people are more af fected by carbon monoxide than others These include pregnant women people with heart or lung disease or anemia those under the influ ence of alcohol and those at high altitudes NA...

Page 4: ...ucts may create a white powder residue within burner box or on adjacent walls or furniture 7 Do not use heater if any part has been under water Immediately call a qualified service technician to inspe...

Page 5: ...s heater has a pilot with an Oxygen Deple tion Sensing ODS safety shutoff system The ODS pilot shuts off the heater if there is not enough fresh air PIEZO IGNITION SYSTEM This heater is equipped with...

Page 6: ...n 2 Remove all protective packaging applied to heater for shipping 3 Check heater for any shipping damage If heater is damaged promptly inform dealer where you bought heater Water vapor is a by produc...

Page 7: ...Theairthatleaksarounddoorsandwindowsmay provide enough fresh air for combustion and ven tilation However in buildings of unusually tight construction youmustprovideadditionalfreshair Unusually tight c...

Page 8: ...r Do not include direct vent gas appli ances Direct vent draws combustion air from the outdoors and vents to the outdoors AIR FOR COMBUSTION AND VENTILATION 30 000 26 000 56 000 DETERMINING FRESH AIR...

Page 9: ...if the building is of unusually tightconstruction provide adequate combustionand ventilation air by one of the methods described in the National Fuel Gas Code ANSI Z223 1 NFPA 54 the International Fu...

Page 10: ...in high traffic areas in windy or drafty areas WA R N I N G M O D E L MN060HBA ONLY When installed in a bathroom do not use flammable products such as aerosol hair spray or any productthatcontainsfla...

Page 11: ...l Of Heater Mounting Bracket Pull Out Hole for Installing Clip CEILING 36 Minimum 6 Minimum From Sides of Heater Left Side Right Side 2 Minimum to Top Surface of Carpeting Tile or Other Combustible Ma...

Page 12: ...1 2 thick or solid walls do not pop open wings 5 Place mounting bracket onto wall Line up last hole on each end of bracket with wall anchors 6 Insert mounting screws through bracket and into wall anch...

Page 13: ...ounting screw into wall stud drill holes at marked locations using 9 64 drill bit Figure 12 Installing Bottom Mounting Screws Side View Front View 6 Replace heater onto mounting bracket 7 Place spacer...

Page 14: ...lling heater make sure you have the items listed below external regulator for propane LP unit only supplied by installer piping check local codes sealant resistant to natural gas and pro pane LP gas e...

Page 15: ...iping and connections for leaks after installing or servicing Correct all leaks at once WARNING Never use an open flame to check for a leak Apply a mixture of liquid soap and water to all joints If bu...

Page 16: ...3 Push in gas control knob slightly and turn clockwise to the OFF position Note Knob cannot be turned from PILOT to OFF unless knob is pushed in slightly Do not force 4 Wait five 5 minutes to clear o...

Page 17: ...pment shutoff valve is fully open 3 Turn control knob clockwise to the OFF position 4 Wait five 5 minutes to clear out any air Then smell for gas including near the floor If you smell gas STOP Follow...

Page 18: ...e 1 minute before lighting pilot again 8 Turn control knob counterclockwise to desired heating level The main burner should light Set control knob to any heat level between HI and LO CAUTION Do not tr...

Page 19: ...eed for cleaning see Care and Maintenance page 20 or service WARNING Only a qualified service person should service and repair heater This includes maintenance requiring replacement or alteration of c...

Page 20: ...ed air no greater than 30 PSl Your local computer store hardware store or home center may carry compressed air in a can You can use a vacuum cleaner in the blow position If using compressed air in a c...

Page 21: ...ignitor button is pressed in there is no spark at ODS pilot 1 Ignitor electrode is posi tioned wrong Ignitor elec trode is broken 2 Ignitor electrode is not con nected to ignitor cable 3 Ignitor cable...

Page 22: ...t 1 Burner orifice is clogged 2 Burner orifice diameter is too small 3 Inlet gas pressure is too low 1 Clean burner orifice see Care and Maintenance page 20 or replace burner orifice 2 Replace burner...

Page 23: ...lls or furniture 1 When heated the vapors from furniture polish wax carpet cleaners etc turn into white powder residue 1 Turn heater off when using furniture polish wax carpet cleaner or similar produ...

Page 24: ...www usaprocom com 200044 01A 24 PARTS MODEL MN060HBA...

Page 25: ...ed Nut 1 11 MB16002 Control Knob 1 12 NRV81FI 3 Pressure Regulator 1 13 ML079 01 Self Locking Screw 2 14 ML119 01 Pressure Tap 1 15 MB40033 Main Inlet Tube Assembly 1 16 MB40045 ODS Line Assembly 1 17...

Page 26: ...www usaprocom com 200044 01A 26 PARTS MODEL MN100HBA ODS Pilot Assembly...

Page 27: ...rol Valve Fixed Nut 1 11 MB16002 Control Knob 1 12 NRV81FI 3 Pressure Regulator 1 13 ML079 01 Self Locking Screw 2 14 MB40034A Main Inlet Tube Assembly 1 15 MB40056 ODS Line Assembly 1 16 MB40054 Gas...

Page 28: ...www usaprocom com 200044 01A 28 PARTS MODEL MN100TBA ODS Pilot Assembly...

Page 29: ...11 845 4 8x60Z Screws 2 12 MB29003 Grill Guard 1 13 ML079 01 Self Locking Screw 2 14 ML084 03 Middle Panel 1 15 NRV81FI 3 Pressure Regulator 1 16 ML073 02 Ignitor Cable 1 17 MB060 02 Mounting Bracket...

Page 30: ...ntact ProCom Heating Inc at 1 866 573 6074 for information EQUIPMENT SHUTOFF VALVE For all models Equipment shutoff valve with 1 8 NPT tap FLOOR MOUNTING STAND PF09B For locating heater on the floor a...

Page 31: ...ng Inc at 1 866 573 6074 When calling please have your model and serial numbers of your heater ready When Gas Pressure Is Too Low pilot will not stay lit burners will have delayed ignition fireplace w...

Page 32: ...om Heating Inc who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty The heater MUST be installed by a qualified installer in accord...

Reviews: