Ann oil
temp
fault
1: No Annunciation
2:On DO Ann1
3:On DO Ann2
4:On DO Ann3
5:On DO Ann4
If desired, the oil temp fault can
be announced at one of the
annunciation Digital Output.
No
Annun-
ciation
Ann
Fuel
Fault
1: No Annunciation
2:On DO Ann1
3:On DO Ann2
4:On DO Ann3
5:On DO Ann4
If desired, the Low Fuel fault
can be announced at one of the
annunciation Digital Output.
No
Annun-
ciation
Ann
HWT
Fault
1: No Annunciation
2:On DO Ann1
3:On DO Ann2
4:On DO Ann3
5:On DO Ann4
If desired, the High water
temperature fault can be
announced at one of the
annunciation Digital Output.
No
Annun-
ciation
Ann
LLOP
Fault
1: No Annunciation
2:On DO Ann1
3:On DO Ann2
4:On DO Ann3
5:On DO Ann4
If desired, the LLOP fault can
be
announced at one of the
annunciation Digital Output.
No
Annun-
ciation
Ann
RPM
Fault
1: No Annunciation
2:On DO Ann1
3:On DO Ann2
4:On DO Ann3
5:On DO Ann4
If desired, the Over/Under
speed fault can be announced
at one of the annunciation
Digital Output.
No
Annun-
ciation
Announce
Unit
OK
1: No Annunciation
2:On DO Ann1
3:On DO Ann2
4:On DO Ann3
5:On DO Ann4
If desired, the healthiness of the
controller can be announced at
one of the annunciation Digital
Output
No
Annun-
ciation
D. RS-485 Parameter #
Device Id
Modbus device ID
1
1-247
Baud Rate
RS 485 Communication Baudrate
9600
1200
2400
4800
9600
19200
Page - 12
Operating Instructions