Fuel Warn
Level #
25 %
Monitoring value of fuel level below
which fuel level warning is
generated.
Disable*
11-80 %
Fuel Warn
Delay #
10 Sec
Monitoring time of fuel level after
which fuel level warning is
generated.
1-999Sec
Fuel Trip
Level #
15 %
Monitoring value of fuel level below
which fuel level trip is generated.
10-80 %
Fuel Trip
Delay #
10 Sec
Monitoring time of fuel level after
which fuel level trip is generated.
1-999 Sec
LLOP Trip
Level
0.4-
2
8.5Kg/cm
The minimum lubricant oil pressure
on which the engine is allowed to
operate. A drop of pressure below the
set limit shall trigger a fault condition
thereby stopping the engine
2
1.0Kg/cm
Page - 10
Operating Instructions
LLOP
Trip Delay
1-999
Sec
Duration for which the low lubricant
oil pressure can be tolerated.
5
HWT trip
level
o
40-250 C The maximum coolant
temperature up to which the engine
is allowed to operate.
o
95 C