Page - 11
HWT Trip
delay
1-999 Sec
The duration for which the engine
is allowed to operate at
temperature higher than the
above set maximum temperature
5
ChgAlt-
Vbelt
1-999Sec
Disabled
While the engine is running and
the Charging alternator pin is not
pulled low for this duration it is
assumed that either the charging
alternator or V-Belt has failed
thereby generating a fault ondition
and stopping the engine.
Disabled
Crank On
Time
1-10 Sec
The maximum duration for which
the engine can be cranked
continuously. In case engine fails
to start another attempt to start
shall be attempted after some
time.
5
Hooter
On Time
1-999 Sec
Duration for which the hooter
shall be . This setting is only
available if the hooter is assigned
to an DO.
15
Solenoid
On Time
1-60 Sec
The duration for which the Pull
solenoid can be continuously
energized while trying to stop the
engine.
22
Operating Instructions
Auto
Scroll
1: Enabled
2: Disabled
Can be used to stop/start the
automatic scrolling of the display
parameters.
Enabled
C. Annunciation
Setting
It is possible to freely assign digital outputs to different fault. There are four
(ANN1 , ANN2, ANN3 and ANN4) field programmable output.
It is also possible to assign same digital output to more than one fault( e.g.
ANN1 can be assigned to fuel fault and HWT fault both, in this case ANN1
will activate on both the faults.