8 Maintenance and Support
Functional Check
Correct functioning of the Resipod can be checked with the test strip provided . The test strip is
intended to be used by both Resipod models (38 mm,1 .5” and 50 mm spacing) .
The upper row allows the functional check using the full 200 µA range . The lower row allows the
functional check using the reduced 50 µA range . Resistors to the outer pads limit the maximum
current to approx . 20 µA, (only two segments in the current indicator strip are active) .
The expected test results are summarized in the table below:
Current range
Expected test result
38 mm (1.5”) spacing
Expected test result
50 mm spacing
200µA (upper row)
12 (±0 .2) k
Ω
cm
16 (±0 .2) k
Ω
cm
50 µA (lower row)
90 (±1 .8) k
Ω
cm
120 (±2 .4) k
Ω
cm