Pro1 Technologies T855SH Installation Manual Download Page 5

Tech Setup Steps

Adjustment Options

Default

LCD Will Show

Technician Setup Menu

Technician Setup Menu

Tech Setup Steps

Adjustment Options

Default

LCD Will Show

Technician Setup Menu

15

16

20

This feature allows the installer 

to change the calibration of the 

room temperature display. For 

example, if the thermostat reads 

70˚ and you would like it to read 

72˚ then 2.

OFF

This feature will flash a reminder 

after the elapsed run time to 

remind the user to change the 

filter. A setting of  “OFF” will 

disable this feature.

Filter Change

Reminder

You can adjust the filter 

change reminder from “OFF” 

to 2000 hours of runtime in 

50 hour increments.

Tech Setup Steps

Room

Temperature

Calibration

0˚F

You can adjust the room 

temperature display to read 

up to 4˚above or below the 

factory calibrated reading.

Adjustment Options

Default

LCD Will Show

FILTER

OF

0

This thermostat has a technician setup menu for easy installer 

configuration. To set up the thermostat for your particular application:

1.  Press the 

MENU

 button.

2.  Press and hold the  

TECH SET

 button for 3 seconds. This 3 

     second delay is designed so that homeowners do not accidentally 

     access the  installer settings.

3. Configure the installer options as desired using the table below.

     Use the             or              keys to change settings and the 

NEXT 

     

or 

PREV

 key to move from one step to another.  

     

Note:

 Only press the 

DONE

 key when you want to exit the 

     Technician Setup options.

4. Press the 

DONE

 key to exit.

Keypad Lockout Note:

 The selected keypad lockout functionality must 

be activated after exiting tech setup. If you do not perform this 

procedure, all keys will function freely. To lock the keypad hold down 

the        and        keys for 3 seconds.  You will see a lock in the display. To 

unlock the display hold down the         and         keys for 3 seconds.

Tech Setup Steps

Adjustment Options

Default

LCD Will Show

PTAC Medium 

Fan Speed 

Terminal 

(Only displayed 

if PTAC mode is 

ON and PTAC fan 

speeds is set to 3)

This setting will select the 

terminal for medium fan speed 

operations.  The selected terminal 

cannot be used for reversing valve 

operations when heat pump is 

enabled. 

Use the         and         buttons to 

select O/B terminals.

0

The swing setting often called 

“cycle rate”, “differential” or

“anticipation” is adjustable. A 

smaller swing setting will cause 

more frequent cycles and a larger 

swing setting will cause fewer 

cycles.

Cooling 

Swing

The cooling swing setting 

is adjustable from 0.2˚ to 

2˚. For example: A swing 

setting of 0.5˚ will turn the 

cooling on at approximately 

0.5˚ above the setpoint 

and turn the cooling off at 

approximately 0.5˚ below 

the setpoint.

The swing setting often called 

“cycle rate”, “differential”, or 

“anticipation” is adjustable. A 

smaller swing setting will cause 

more frequent cycles and a larger 

swing setting will cause fewer 

cycles.

Heating 

Swing

0.5

0.5˚

The heating swing setting is 

adjustable from 0.2˚ to 2˚. 

For example: A swing setting 

of 0.5˚ will turn the heating 

on at approximately 0.5˚ 

below the setpoint and turn 

the heating off at 0.5˚ above 

the setpoint.

0.4˚

0.4

Swing Setting Tip

The second stage will turn on at 2x the swing setting.  The second stage will 

turn off when 1x the swing is reached. For example, if the swing setting is .5 

degrees for heating and the thermostat is set at 70

˚

F, the first stage will turn 

on at approximately 69.5

˚

F.  The second stage will turn on at 69

˚

F. The second 

stage will turn off at 69.5

˚

F and the first will turn off at 70.5

˚

F.  If the third 

stage is used, it will turn on at 68.5

˚

F and turn off at approximately 69

˚

F.

Technician Setup Menu

You can configure this thermostat 

to have 2 or 4 programmable 

time periods per day. 

Time Periods

(Only displayed if 

program optioin is 

set to 5d or 7d)

4

Pro Recovery

This feature will start heating and 

cooling early to bring the building 

temperature to its programmed 

setpoint by the beginning of the 

WAKE, RETURN and OCCUPIED 

time periods. 

Use the          or           key to 

select on or off. 

ON

Use the         and         buttons to 

select 4, 2C, or 4C time periods 

per day. 

4:  Wake, Leave, Return & 

Sleep. 

2C: time periods are Occupied 

& Unoccupied. 

4C: time periods are Occupied 

1, Unoccupied 1, Occupied 2, & 

Unoccupied 2

Keypad

Lockout Code

(Only displayed 

if keypad lockout 

is set to Basic, 

Partial, or Full)

Keypad lockout with code shows 

only when Keypad Lock is set to 

BASIC, PARTIAL or FULL

OFF

1.  When ON you must enter 

the code after pressing the     

        and         buttons toegether 

for 3 secounds to take the 

thermostat in or out of keypad 

lockout.  You will then be taken 

to a screen that allows you to 

enter the code.  

2.  Use         and         to change 

each number.  Use the Previous 

and Next keys to change from 

one number to the next.  The 

number you are currently on 

will blink.  

3.  Press Done when 

completed.  If entered correctly 

the thermostat will be re-

moved from keypad lockout. 

You can configure this thermostat 

to have a 7 day program, a 

5+1+1 program or No program. 

Note: If 7d is selected, in set schedule 

you will program all seven days 

individually. 

 If 5d is selected, in set schedule 

you will program Monday – Friday 

together and Saturday and Sunday 

individually. 

If 0d is selected the thermostat 

becomes non-programmable and 

the Set Schedule button goes away 

in Menu.

Program 

Options

Use the         and         button 

to select 7d for 7 day, 5d for 

5+1+1, or 0d for 

non-programmable. 

5d

19

COOL SWING

HEAT SWING

MED FAN TERM

CALIBRATE

PTAC Mode

This setting allows the thermostat 

to operate a PTAC. This will allow 

for multiple fan speeds selectable 

in the next two tech settings.

Use the         and         buttons to 

select ON/OFF.

ON

OF

PTAC MODE

This setting allows you to choose 

the number of fan speeds the 

thermostat will control.  

G = Low Speed Fan

B/O = Medieum Speed Fan

Y2 = High Speed Fan

PTAC Fan

Speeds

(Only displayed if 

PTAC mode is ON) 

2

2

FAN SPEEDS

When turned on the thermostat 

will operate a heat pump.  EM. 

Heat will show as an option in the 

system switch tech setting.  

Use the         and         button to 

adjust.  

Heat Pump

OFF configures the 

thermostat for conventional 

systems. 

ON configures the 

thermostat for heat pump 

systems.

OFF

OF

HEAT PUMP

PROGRAM

5d

4

TIME 
PERIODS

PRO 
RECOVERY

This setting maximizes efficiency 

and equipment longevity by 

increasing the heating and 

cooling swing settings to 2° 

during the unoccupied and leave 

time periods.  This will result in 

significantly fewer system cycles.

OFF

CYCLE MIN

OF

Keypad 

Lockout

Keypad lockout allows you to 

configure the thermostat so some 

or all of the keys don’t function. 

Use the        and         buttons to 

select  OFF,  BASC,  PART,  FULL                                           

OF - OFF= keypad lock-

out has been disabled.                                                             

BA - BASIC = basic keypad 

lockout  locks  the  menu  key.                                                    

PA - PARTIAL= partial keypad 

lockout, which locks all the 

keys except the or setpoint 

keys. 

FU - FULL= full keypad 

lockout, which locks out all 

the keys.                                                                                                              

OFF

KEY 
LOCKOUT

OF

OF

KEY CODE

Use the         and         buttons to 

select , 2 or 3.

1. Speeds: ON, Auto

2. Speeds: Low, High, Auto

3. Speeds: Low, Med, High, 

Auto

Use the          or           key to 

select on or off. 

Default Heat Heat Options Cool Default

Cool Options

PTAC (conventional)

PTAC (Heat Pump)

Heat Pump

Conventional

System Mode

1

2

2

2

1

2, 1

5, 4, 3, 2, 1

2, 1

1

1

2

2

1

1

3, 2, 1 

3, 2, 1 

Cycle 

Minimizer

(Only displayed if 

program optioin is 

set to 5d or 7d)

Summary of Contents for T855SH

Page 1: ...ld be flush with the wall 4 Wires should be pushed into the wall Installation Tips The thermostat should be installed approximately 4 to 5 feet above the floor Select an area with average temperature...

Page 2: ...at or cool is on 2 will appear for the third stage of heat Setpoint Displays the user selectable setpoint temperature Hold is displayed when the thermostat program is permanently overridden System Ope...

Page 3: ...lay a jumper can be installed between E and W2 Magnet in door Use the bevel on lower ridge Thermostat Quick Reference The low battery icon is displayed when the AA battery power is low Whenever the th...

Page 4: ...t OFF 5 10 15 30 45 60 or 90 minutes STAGING DELAY OF This feature allows the installer to select the minimum run time for the compressor For example a setting of 4 will force the compressor to run fo...

Page 5: ...t will turn on at 68 5 F and turn off at approximately 69 F Technician Setup Menu You can configure this thermostat to have 2 or 4 programmable time periods per day Time Periods Only displayed if prog...

Page 6: ...o select OFF LOW or HIGH OFF configures the display light to come on when the light key or any button is pressed LOW configures the display light to stay on at a low intensity constantly When a button...

Page 7: ...oor sensor 35 120 HIGH LIMIT Use the or keys to select the Low Limit for the floor sensor 35 120 50 86 86 50 LOW LIMIT OF OFF FREE COOLING The temperature of the floor sensor will be displayed Note On...

Page 8: ...79 6 80 6 73 8 74 7 75 7 77 2 78 2 80 2 81 2 82 7 75 2 76 3 77 3 78 8 79 8 81 8 82 8 84 3 76 1 77 1 78 1 79 9 80 9 83 4 84 4 86 2 77 78 79 81 82 85 86 88 77 9 79 1 80 3 82 3 83 6 86 6 88 3 91 78 7 80...

Page 9: ...below HUM Terminal Onlyshowsif humidifyisset to on Usetheleftandrightarrowsto selectoneofthefouroptions ViewtheHUMterminalchart belowforanexplanationof theseoptions ON HUM TERMINAL 1 3 Options for ho...

Page 10: ...he WAKE OCC1 time period for the weekday setting 4 Time is flashing Use the or key to make your time selection for the weekday WAKE OCC1 time period Note If you want the fan to run continuously during...

Page 11: ...hat day s WAKE OCC1 time period Note If you want the fan to run continuously during this time period select ON with the FAN key If you want to use IAQ mode during this time period select IAQ with the...

Page 12: ...splay HOLD and RUN SCHED on the bottom of the screen when you press the or key If you do nothing the temperature will remain at this setpoint temporarily for 4 hours The program setpoint will then rep...

Reviews: