![Pro Lite LD64 Installation, Servicing And User Instructions Manual Download Page 3](http://html1.mh-extra.com/html/pro-lite/ld64/ld64_installation-servicing-and-user-instructions-manual_1604388003.webp)
Technical Installation Information
Note * 13A Fuse Rating: The unit must be protected by a 13 amp fuse if a 13 amp plug is used.
If another type of plug is used, a 15A fuse requires to be used in the plug, adaptor or distribution
board.
Base Unit
- 600mm (W) x 550mm (D) x 650mm (H)
Side & Rear Clearance
- 150mm
Weight
- 41kg
Power Rating
- 2.65kW
Fuse
- 13 amp
SECTION 1 - SITING
PRO-LITE models have been designed in a modular form which consists of base, counter and free-
standing units.
Information which relates to the ovens is listed above.
Free-standing and base models should be installed upon a firm, level surface and adjustable feet are
provided for levelling purposes.
Counter units must be positioned upon a table, counter or similar surface.
Vertical and horizontal clearances required from the top and sides of a particular unit to any
overlying combustible surface (ie wall, partition, etc) are also listed above. Relevant fire regulations
must be complied with.
Mounting Counter Units on an Oven
When mounting a counter unit upon the LD62 and LD64 ovens, it is recommended that units which
carry liquids, i.e. fryers and bains marie, are secured as follows:
Remove oven outer back panel.
Remove oven crown plate.
Position unit(s) which require to be secured upon the oven.
Secure hob unit(s) to oven through side flange centre holes into the threaded inserts in the base(s)
of the hob unit(s). Use fixings provided (packed separately) and replace oven back panel.
The unit is now ready for electrical connection.
SECTION 2 - ELECTRICAL SUPPLY AND CONNECTION
Electrical ratings are as stated on the unit data plate. The listing in Table 1 is based on standard UK
specification at 230V~. Wiring must be executed in accordance with the regulations listed in this
booklet.
WARNING: Each individual appliance must be earthed!
The appliance is also provided with a terminal for the connection of an external
equipotential conductor. This terminal is in effective electrical contact with all fixed
exposed metal parts of the appliance, and shall allow the
connection of a conductor
having a nominal cross-sectional area of up to 10 mm². It is located on the rear panel and
is identified by the following label and must only be used for bonding purposes.
Summary of Contents for LD64
Page 8: ...LD64 WIRING DIAGRAM ...