background image

2

General Specifications

General Specifications

Electrical Specifications

Environmental Specifications

External Specifications

NOTE:  

• Extending the length of the USB cable can degrade (weaken) signals, causing the potential for 

errors. Do not extend the cable.

• Use only the SELV (Safety Extra-Low Voltage) circuit to connect the USB and Ethernet interface.

Connector type

Ethernet I/F

Modular jack (RJ-45), IEEE802.3i/IEEE802.3u, 

10BASE-T/100BASE-TX

USB I/F

Type A (plug), USB 2.0 High-Speed (480 Mbps)

Po

we

sup

p

ly

Rated input voltage

5 Vdc (powered from USB bus)

Input voltage limits

4.75...5.25 Vdc

Power consumption

0.63 W or less

P

h

ysical e

n

viron

m

en

t

Ambient air operating 

temperature

0...55 °C (32...131 °F)

Storage temperature

-20...60 °C (-4...140 °F)

Ambient air and storage 

humidity

10...90% RH (non condensing, wet bulb temperature 39 °C 

[102.2 °F] or less)

Dust

0.1 mg/m

3

 (10

-7

oz/ft

3

) or less (non-conductive levels)

Pollution degree

For use in Pollution Degree 2 environment

Atmospheric pressure 

(Operating altitude)

800...1,114 hPa (2,000 m [6,561 ft] or lower)

Mech

an

ic

al

 

en

vi

ro

nm

en

t

Vibration resistance

IEC/EN 61131-2 compliant

5...9 Hz Single amplitude 3.5 mm (0.14 in)

9...150 Hz Fixed acceleration: 9.8 m/s

2

X, Y, Z directions for 10 cycles (approximately 100 minutes)

Concussion resistance

IEC/EN 61131-2 compliant

(147 m/s

2

, X, Y, Z directions for 3 times)

El

ect

ri

ca

en

vi

ro

nm

en

t

Electrical fast transient/burst

IEC 61000-4-4

2 kV: Power port (display unit)

1 kV: Signal ports

Electrostatic discharge immunity

Contact Discharge Method: 6 kV

Air Discharge Method: 8 kV

(IEC/EN61000-4-2 Level 3)

External dimensions (W x H x D)

105 x 40 x 27 mm (4.13 x 1.57 x 1.06 in)

Cable length

0.5 m (1.64 ft) (including connections)

Weight

100 g (0.22 lb) or less 

Summary of Contents for PFXZCGEUUE1

Page 1: ... DANGER HAZARD OF ELECTRIC SHOCK OR EXPLOSION Do not disassemble or remodel this product in any way Doing so may cause an electric shock or fire Do not use this product in areas where flammable gases are present Doing so may cause an explosion Do not allow water to enter the connector Do not touch the connector with wet hands Doing so may cause an electric shock Failure to follow these instruction...

Page 2: ...orage humidity 10 90 RH non condensing wet bulb temperature 39 C 102 2 F or less Dust 0 1 mg m3 10 7 oz ft3 or less non conductive levels Pollution degree For use in Pollution Degree 2 environment Atmospheric pressure Operating altitude 800 1 114 hPa 2 000 m 6 561 ft or lower Mechanical environment Vibration resistance IEC EN 61131 2 compliant 5 9 Hz Single amplitude 3 5 mm 0 14 in 9 150 Hz Fixed ...

Page 3: ...section Pin Arrangement Pin Signal Name Meaning 1 TX Output Send Data 2 TX Output Send Data 3 RX Input Receive Data 4 NC No connection 5 NC No connection 6 RX Input Receive Data 7 NC No connection 8 NC No connection Shell FG Functional Ground common with SG Color Indicator Description Green Active Flashing Data transmission is occurring OFF No data transmission Green Link ON Data transmission is a...

Page 4: ...age below Attaching directly to the Display Unit When attaching this product on the rear side of the display unit among the 4 screws shown in the diagram below use 2 horizontally positioned or 2 vertically positioned screws to attach this product If the display unit already has an attachment it may restrict the direction in which you can place this product 105 4 13 mm in 27 1 06 500 19 68 40 1 57 ...

Page 5: ... attachment position Attach this product to a stable surface Do not leave it hanging by its cord Be careful with wire placement If this product s cable overlaps with other cables excessive noise could cause a malfunction Install this product in an enclosure with mechanical rigidity This product is not designed for outdoor use UL certification obtained is for indoor use only Make sure this product ...

Page 6: ...AGE Power off this product before cleaning it Do not use paint thinner organic solvents or a strong acid compound to clean the unit Failure to follow these instructions can result in equipment damage I9 0 35 0 7 0 03 2 7 0 11 I 3 3 0 13 M3 screw 6 5 0 26 75 2 95 2 x M3 mm in 4 0 16 A급 기기 업무용 방송통신 기자재 이 기기는 업무용 A 급 전자파적 합기기로서 판매자 또는 사용자는 이 점을 주의하시기 바라며 가정 외의 지역에서 사용하는 것을 목적 으로 합니다 DANGER RISQUE D E...

Page 7: ...2 㿺ᇐⲺ䲆䠅㾷 ԛсȾ hφ㺞 䈛ᴿᇩ 䍞㠩ቇ 䈛䜞ԬⲺḆжൽ䍞ᶆᯏѣⲺ 䠅䎻 GB T 26572 㿺ᇐⲺ䲆䠅㾷 Ⱦ This table is made according to SJ T 11364 ȖφIndicates that the concentration of hazardous substance in all of the homogeneous materials for this part is below the limit as stipulated in GB T 26572 hφIndicates that concentration of hazardous substance in at least one of the homogeneous materials used for this part is above the limit as s...