![Pro-face GP-4000M Replacement Manualbook Download Page 10](http://html1.mh-extra.com/html/pro-face/gp-4000m/gp-4000m_replacement-manualbook_1605188010.webp)
10/34
2.7 Interface
2.7.1 Serial Interface
For the COM ports of ST3000 series and GP-4201TM, the signal of the serial port is
different. To know the details about them, see [
] and [
4.3
Signals of COM ports
].
Because of it, the existing PLC connection cables cannot be used as they are. If you
use the existing connection cables, see [
4.5 Cable Diagram at the time of
When the both COM1 and COM2 ports on ST3000 series have setting, devices can be
connected to the COM1 port only after replacement with GP-4201TM.
- When the COM1 port is used for RS-232C connection and the COM2 port for
RS-422/485 connection:
Replace with GP-4201TW instead of GP-4201TM.
- When the both COM1 and COM2 ports are used for RS-422/485 connection:
Please contact our sales office in your region.
(
http://www.pro-face.com/customer/contact.html
2.7.2 CF Card Interface
GP-4201TM is not equipped with a CF card slot. You can use an USB storage device
instead of a CF card but GP-4201TM supports the function of saving sampled data in
CSV only (GP-Pro EX Ver. 3.01 or later is required).
You can use the storage devices below instead after replacement:
GP-4301T
SD card
GP-4301TW
USB storage device
2.8 Clock
There’s no battery in GP-4201TM. When the GP’s power is turned OFF, the clock data
is reset. Using the Clock Update Settings of GP-Pro EX allows you to take in the clock
data of the connected device. For details, refer to 5.2 Adjusting the Time in the
GP-Pro EX Reference Manual.