CLEANING AND MAINTENANCE

• 

Clean the product with a soft, dry cloth only. Do not use any solvents or abrasive 

chemical cleaners.

• 

The LED lamps in this product are non-replaceable.

 

Changing the battery

• 

If after a routine operation check, the lamp does not remain lit for the 3 hour period, 

a new battery pack may be required. Change the battery pack as follows:

1. 

Isolate from the mains supply.

2. 

Remove the front panel.

3.  Unplug the battery pack connector from the PCB.

4. 

Remove the old battery pack. 

5.  Write the current date on the new battery pack.

6.  Secure the new battery pack in position and connect the wiring terminal connector.

7. 

Refit the cover. Make sure that the screws are securely fastened.

8. 

Restore mains power and allow to charge for 24 hours.

9.  Perform the full operation check and update the test record.

OPERATIONAL CHECKS

Note:

 This equipment must be checked regularly in compliance with local regulation and 

codes of practice. For your own safety, testing should occur during the day. 

The LED’s can be tested by pressing the TEST button on the bottom of the case.

• 

After installation, you should allow 24 hours for the battery pack to charge fully 

before testing. 

• 

Isolate the power supply and check that the lamp remains illuminated for at least 

three hours. Restore the power supply.

• 

Each day: Check that the green charging LED is lit.

• 

Each month (short test): Isolate the power supply and check that the lamp remains 

illuminated. Record the results on the test record sheet included with these 

instructions.

• 

Every six months: Isolate the power supply and check that the lamp remains 

illuminated after 1 hour. Record the results on the included test record. 

• 

Once each year: Isolate the power supply and check that the lamp is still illuminated 

after 3 hours. Record the results on the included test record.

 

Please keep these test records in a safe place. A fire officer or other authorised 

person may want to see your record of inspection and testing.