Installing the door element 

 

 

Turn the door element into the installation 
position and place it in front of the wall 
opening. 

 

Route the connection cable hanging on the 
lock side towards the front and let it hang. 

 

Lift the door element into the wall opening 
and place on the protruding packer 
material at the bottom. 

 

Firstly, the door frame must be pushed 
against the bottom side packer material. 

 

Align the door element flush with the 
mounting frame, secure it against falling 
out and tilting. 

 

The four bottom countersunk head screws 
4.5 x 80mm  are then tightened and then 
the frame is aligned using the cross-line 
laser. 

 

Use the countersunk head screws 4.5 x 
80mm to screw the remaining frame of the 
door element onto the mounting frame. 

 

After screwing the frame onto the 
mounting frame the door leaf can be 
opened. 

 

A power adapter with 24V or a test device 
is required for this. White cable +24V, 
brown cable -24V. 

 

Screw the nameplate onto the mounting 
frame, in the middle of the opening side, 
using a panhead screw 4.5 x 20mm. 

 

After the functional test, lay the connection 
cable in the shaft between the mounting 
frame and the wall (see detail below). 

 

Fill the wall edge joints with mortar or 
gypsum (e.g. Knauf Uniflott) depending on 
the wall type. 

 

 

 

 

 

connecting 

cable 

Summary of Contents for PRIODOOR ETX-RDA

Page 1: ...Assembly and Operating Instructions PRIODOOR ETX RDA Air release shutter for pressure differential type smoke control systems opening on the shaft side Dated 05 2021 EP A 10154 4...

Page 2: ...l to comply with the instructions We expressly reserve the right to make technical changes even without separate announcement which serve to improve our product or which are caused by changes in legis...

Page 3: ...6 Assembling the mounting frame 7 Installing the mounting frame 7 Installing the door element 9 Installation detail ETX RDA in solid wall 10 Installation detail ETX RDA in PRIOWALL 11 Connector 11 Eme...

Page 4: ...umb and horizontal A cross line laser must be used for the installation When putting down individual parts do not place them on their corners and layout the storage area with soft material beforehand...

Page 5: ...the recognised rules of safe practice They may only be used for their intended purpose in indoor areas and only used if they in a faultless safe condition Any other use is deemed not to be as intende...

Page 6: ...ction may only be made following consultation with PRIORIT as otherwise the approval warranty expires The warranty for installation work must be provided by the installer Warranty and liability claims...

Page 7: ...ls against falling Place the mounting frame in the wall opening Align vertically plumb and horizontally Arrange the all round opening gap uniformly Place packer material under the screw fixing points...

Page 8: ...e Fill the void between the mounting frame and the wall opening with gypsum We recommend using our packer blocks made of non combustible PRIODEK H to install the product Packer is available in our pro...

Page 9: ...ews 4 5 x 80mm are then tightened and then the frame is aligned using the cross line laser Use the countersunk head screws 4 5 x 80mm to screw the remaining frame of the door element onto the mounting...

Page 10: ...ction cable exit position Make sure that the connection cable is not damaged when drilling Guide the connection cable through the drillhole in the shaft Installation detail ETX RDA in solid wall Mount...

Page 11: ...bracket which holds the chain drive is screwed IMPORTANT Do not use a cordless screwdriver use a manual screwdriver instead Move the door manually in the direction of the shaft Repair or replace the...

Page 12: ...12 Technical information on the chain drive excerpts...

Page 13: ...13...

Page 14: ...14...

Page 15: ...15...

Page 16: ...16 Chain motor technical data...

Page 17: ...17...

Page 18: ...d seals make good if necessary and prepare the corresponding report 5 Confirm that the ETX RDA is opened and closed by the control system and observe the ETX RDA make good if necessary and prepare the...

Page 19: ...completeness replace seals if necessary Comments Final remark Condition of the installation New Good Poor System ready for operation Yes No Inspected by Date Name Signature With my signature I confir...

Page 20: ...RDA with an external electricity source Check the wiring on site The ETX RDA does not open or close correctly or does not function after checking the above points Error in the control of the chain dri...

Page 21: ...21 Notes...