![Primex OneVue Sense A100 Installation Manual Download Page 6](http://html1.mh-extra.com/html/primex/onevue-sense-a100/onevue-sense-a100_installation-manual_1601798006.webp)
Segment
Description
Temperature (°F or
°C)
The last sampled ambient temperature reading in either Fahrenheit or Celsius. A sample reading it taken every 60 seconds.
The display units (°F or °C) is configured within the sensor profile in your OneVue account.
Humidity (%RH)
The last sampled relative humidity reading; RH%
The LCD display alternates between the sampled temperature and humidity readings every 15 seconds.
No Signal
Indicates the last check-in to your OneVue account failed.
For wireless network use, a failed check-in may be due to the device is not within range of a wireless signal or the wireless
signal strength is not adequate for normal operation. For PoE or Ethernet use, a failed check-in may be due to a network
connection cannot be established.
If the device is powered by AC or Power over Ethernet (PoE), the yellow LED indicator flashes during this state.
Signal Ok
Indicates the last check-in to your OneVue account was successful.
LOW -Battery Level
The device is in an Alarm state due to its estimated battery life is less than 25%.
From the start date of this state, its estimated battery life remaining is 30 days. This estimation is based on the use of lithium
1.5V batteries, 1 hour Logging Interval, 8 hour Check-In Interval, and adequate wireless signal.
If the device is powered by AC or Power over Ethernet (PoE), the yellow LED indicator flashes during this state.
Lbat
The device is an Alarm state due to its battery level is critically low.
Readings are not logged or transmitted your OneVue account during this state.
Up
A firmware update is being applied to the device.
Readings are not displayed, sampled, or logged during this mode.
Con
The device is in configuration mode. The config icon is also displayed.
Readings are not displayed, sampled, or logged during this mode.
Temperature and Humidity Sensor service buttons
A OneVue Temperature and Humidity Sensor has two service buttons located on the front of the device.
Silence
Button
The silence button clears the local reading alarm.
During a reading Alarm state, pressing and immediately releasing the silence button clears the audio alert and stops the red LED from
flashing, but does not acknowledge the alert in your OneVue account.
Audio alert resumes once the time period of the Resume Audio Alert setting has been reached. Audio alert settings are configured from
a sensor's gateway profile.