2. Sensor settings (Go go Monitoring > Monitored Assets > select Monitored Asset > select sensor.
• Normal Condition
The Normal Condition is the expected, operating range or condition of the Monitored Asset assigned to the
sensor. The settings vary based on the type of sensor and the condition being monitored.
• Alarm Delay
Alarm Delay sets the amount of time OneVue delays setting the sensor and its assigned Monitored Asset to an
Alarm state. When a sensor reading is not within its Normal Condition (an Out of Range status) and it remains
Out of Range for the time period set in its Alarm Delay setting, the sensor and Monitored Asset are then set to an
Alarm state with a status of Out of Range, Past Alarm Delay.
• Audio Alert (sensor gateway setting)
Primex sensors are equipped with an audio alert that is activated during a reading Alarm state (Out of Range,
Past Alarm Delay status). The audio alert is activated when a reading is out of range and the time period it has
been out of range has exceeded the time period set in its Alarm Delay.
• Logging Interval (sensor gateway setting)
The Logging Interval is how frequent a sensor logs a reading and stores it into its internal memory. All logged
readings are then sent to OneVue at the frequency set the sensor's Check-in Interval frequency.
• Check-in Interval (sensor gateway setting)
The Check-in Interval is the frequency a sensor connects to the facility's network to sends its logged readings to
OneVue. Also, during each check-in, pending setting updates are downloaded to the sensor.
• Unresponsive Timeout (sensor gateway setting)
The Unresponsive Timeout is the maximum amount of time a Primex device can go without a check-in to
OneVue. When this time limit is exceeded, the device is set to an Alarm state with an Unresponsive status.