connected. While these ratings provide a wide range of installation options, Primex recommends advance testing of
any bell system prior to extensive product installation and conversion from any current solution.

• When using multiple bell controllers to control different sets of bells within a facility, testing should be always be

performed to confirm proper operation and to verify there is no bleed-over between multiple bell controllers. To
prevent bleed over from occurring, the best practice is to have a single bell controller per branch circuit.

• Bell controller terminals accept wire gauge from 16-26 AWG.
• When wiring the bell controller to a public address (PA) and/or bell system equipment, all power to the device and

equipment must be turned off.

• Bell controller must be installed indoors.
• Bell controller must not be used for medical, life-saving purposes, or for any purpose where its failure could cause

serious injury or the loss of life.

• Bell controller must not be used in any way where its function or failure could cause significant loss or property

damage.

• Bell controller must be configured with your OneVue account ID and network settings. Verify the device can

successfully connect to the network and check-in to OneVue at its install location.

Install location guidelines

When identifying the mounting location of a bell controller, consider the following guidelines.

• Requires a hardwired connection from the bell controller's terminal block to an existing PA or bell system, the two

must be in close proximity to each other.

• Wired Ethernet use: network port jack is located in close proximity to the install location.
• Power over Ethernet (PoE) use: PoE compliant network port jack is located in close proximity to the install location.
• AC power: an outlet is within 5 feet (1.52 m) from the install location.
• Install location is easily accessible for maintenance and clear from obstructions.
• Bell controller is shock and vibration resistant; however, be careful not to drop or install the device in a location

where it could be exposed to excessive vibration.

WARNING

Battery power is for backup use only. When solely operating on battery power (two AA Lithium 1.5V
batteries) its estimated battery life is up to a maximum of 24 hours.

Connect bell controller relays to public address (PA) or bell system

A Bell Controller has two independent relays that can be connected to your existing PA or school bell system. Each of
the relays has a separate Normally Open (NO) and Normally Closed (NC) input.

The removable terminal connector is provided for simple wiring. The wiring procedure is as follows:

1. Be sure to follow the installation requirements and installation location guidelines.
2. All power to the device and PA or bell system equipment must be turned off.

Page 10

Summary of Contents for OneVue Notify E130

Page 1: ...Notify Bell Controller Installation Guide OneVue Notify Bell Scheduling Publication date April 9 2021...

Page 2: ...e is a trademark of Primex All other trademarks are the property of their respective owners Primex is the leading provider of solutions to automate and maintain facility compliance increase efficienci...

Page 3: ...contents 9 Install requirements 9 Install location guidelines 10 Connect bell controller relays to public address PA or bell system 10 Connect bell controller to dry contact switch for an impromptu be...

Page 4: ...VAC 50 60 Hz 0 4A Output 5V DC 1 0A max Optional power extension cable USB power cable 6 5 feet 2 m Mini B 5 pin M and Mini B 5 pin F connector Power over Ethernet PoE compliant with IEEE 802 3af sta...

Page 5: ...to activate a non scheduled event impromptu bell Connected to an external dry contact closure switch or button On board clock synchronizes its time with an NTP time source to ensure bell schedule acc...

Page 6: ...ch or button to activate a bell manually commonly referred to as an impromptu bell An impromptu bell is a bell event that is not scheduled in OneVue Terminal block connections pin out specifications T...

Page 7: ...than 3 hours It s scheduled to check in hourly For wireless network use a failed check in may be due it is not within range of wireless access point or the wireless signal strength is not adequate for...

Page 8: ...cal Support to assist with troubleshooting the cause of the failure Service buttons A Bell Controller has two service buttons located on the front of the device Button Icon Use Silence During an Alarm...

Page 9: ...kup for up to a maximum of 24 hours 4 3M Dual Lock Tape 2 x 1 strip 1 USB configuration cable supplied with each device order only For use with the Primex Device Configuration software to manually con...

Page 10: ...nes When identifying the mounting location of a bell controller consider the following guidelines Requires a hardwired connection from the bell controller s terminal block to an existing PA or bell sy...

Page 11: ...ch or button to activate a bell manually commonly referred to as an impromptu bell An impromptu bell is a bell ring event that is not scheduled in OneVue The removable terminal connector is provided f...

Page 12: ...he bell controller AC or PoE 10 When power was applied the device automatically initiated a check in to OneVue Verify its LCD displays Signal OK which indicates it successfully checked in to OneVue If...

Page 13: ...bell controller AC or PoE 11 When power was applied the device automatically initiated a check in to OneVue Verify its LCD displays Signal OK which indicates it successfully checked in to OneVue If th...

Page 14: ...an electrical hazard and may damage the device while nullifying its warranty Equipment Precautions To avoid possible electric shock or damage make sure device is not powered during installation or mo...

Page 15: ...or compliance could voice the user s authority to operate this equipment Example use only shielded interface cables when connecting to computer or peripheral devices FCC Warning Any Changes or modific...

Page 16: ...ructure mode Wireless Stations normally scan all Channels looking for an Access Point If more than one Access Point can be used the one with the strongest signal is used This can only happen within an...

Page 17: ...en altered or modified in any way including but not limited to attempted warranty repair other than by Primex or an authorized service partner LIMITATION OF LIABILITY The warranties and remedies conta...

Page 18: ...s technical support services for Primex products If you have purchased Primex products or have a service agreement with a Primex Partner they are your primary contact for all Technical Support inquire...

Reviews: