Error code Table-1
Error Condition
Error Code
Indication
AC voltage high
E1
Step1: Check environmental condition, AC
Voltage and Frequency.
Step2: Check the LCM AC Voltage and
Frequency Setting Range.
Step3: If environmental condition is over
the inverter setting.
Please adjust related parameters.
AC voltage low
E2
AC absent
E3
AC frequency high
E4
AC frequency low
E5
DC voltage high
E6
Step1: Check the panel voltage, Is it within
the operating range?
Step2: If the PV Voltage is over 1000V,
Please adjust the number of panel
connections.
PV insulation low
E7
Step1: Confirm that the panel has abnormal
impedance to the earth.
Step2: If the error code is happened in the
early morning or dusk.
It is parasitic capacitance connect Panel
with earth, It is a normal phenomenon.
Step3: If it continues to occur, please
replace another inverter.
Ground current
high
E8
Step1: Confirm that the panel has abnormal
impedance to the earth.
Step2: If the error code is happened in the
early morning or dusk.
It is parasitic capacitance connect Panel
with earth, It is a normal phenomenon.
Step3: If it continues to occur, please
replace another inverter.
Summary of Contents for PV T U Series
Page 11: ...9 Product Labels ...
Page 16: ...14 6 1 Assembly Chart PV 10000T U PV 15000T U PV 20000T U PV 30000T U PV 40000T U ...
Page 27: ...25 PV 10000T U PV 15000T U PV 20000T U Only PV 15000T U need to add EMI core at ground cable ...
Page 31: ...29 PV 10000T U PV 15000T U PV 20000T U PV1 PV1 PV2 PV2 PV1 PV2 PV2 PV1 PV1 PV1 PV2 PV2 ...
Page 67: ...65 12 Addendum Efficiency Charts PV 10000T U PV 15000T U ...
Page 68: ...66 PV 20000T U PV 30000T U ...
Page 69: ...67 PV 40000T U ...