28
Closing the Front Cover
After connecting all wires, please
1.
Inspect all the connections again.
2.
Close front cover and tighten 4 screws gently.
The torque should not exceed 30kgf-cm.
3.
Check for any openings in between front
cover and inverter.
DC (PV) Wiring
1.
DC Input Ratings
MODEL
Rating
PV-
10000T-U
PV-
15000T-U
PV-
20000T-U
PV-
30000T-U
PV-
40000T-U
Recommended
Max. DC Power(W)
<12000
<18000
<24000
<36000
<48000
Max. DC (V)
1000
1100
Max. Current (A)
11.5A/string 1
11.5A/string 2
23A in total
23A/string 1
11.5A/string 2
34.5 A in total
23A/string 1
23A/string 2
46 A in total
35A/string 1
35A/string 2
70 A in total
35A/string 1
35A/string 2
70 A in total
MPPT
(Input Pairs)
2
(2 inputs)
2
(3 inputs)
2
(
4 inputs)
2
(6 inputs)
2
(6 inputs)
2.
Use either of the following recommended connectors
1.
Multi-Contact MC4
2.
Wieland PST40i1C
3.
Connect to PV Array
After all the associated cables and connectors have been prepared
1.
Remove sealing plugs as depicted as below.
2.
Plug in PV cables gently as depicted below
②
Sealing plug
Sealing plug
Summary of Contents for PV T U Series
Page 11: ...9 Product Labels ...
Page 16: ...14 6 1 Assembly Chart PV 10000T U PV 15000T U PV 20000T U PV 30000T U PV 40000T U ...
Page 27: ...25 PV 10000T U PV 15000T U PV 20000T U Only PV 15000T U need to add EMI core at ground cable ...
Page 31: ...29 PV 10000T U PV 15000T U PV 20000T U PV1 PV1 PV2 PV2 PV1 PV2 PV2 PV1 PV1 PV1 PV2 PV2 ...
Page 67: ...65 12 Addendum Efficiency Charts PV 10000T U PV 15000T U ...
Page 68: ...66 PV 20000T U PV 30000T U ...
Page 69: ...67 PV 40000T U ...