FAN FILTER UNIT
INSTALLATION INSTRUCTIONS
POTENTIOMETER
(POT)
MEASURE (+) VDC
MEASURE (-) VDC
Step 1:
Determine test point voltage (VDC) from the formula based on the desired airflow using the appropriate chart below.
Supply - Constant Flow – Clean Filters (Forward Curved)
Voltage Velocity
24x24
24x36
24x48
Volt
FPM
BTR - FC
RSR - FC
BTR - FC
RSR - FC
BTR - FC
RSR - FC
115
45-135
VDC =
VDC =
VDC =
VDC =
VDC =
VDC =
240
45-135
VDC =
VDC =
VDC =
VDC =
VDC =
VDC =
277
45-135
VDC =
VDC =
VDC =
VDC =
VDC =
VDC =
Supply - Constant Torque – Clean Filters (Backwards Curved)
Voltage
Velocity
24x36
24x48
Volt
FPM
BTR - BC
RSR - BC
BTR - BC
RSR - BC
115
45-135
CFM + 233
449
VDC =
CFM + 267
437
VDC =
CFM + 226
486
VDC =
CFM + 302
517
VDC =
240
45-135
CFM + 240
450
VDC =
CFM + 193
393
VDC =
CFM + 185
459
VDC =
CFM + 313
522
VDC =
277
45-135
CFM + 233
444
VDC =
CFM + 208
399
VDC =
CFM + 165
448
VDC =
CFM + 307
512
VDC =
CFM-71
145
CFM-50
96
CFM-45
97
CFM-48
95
CFM-39
67
CFM-39
67
CFM-31
67
CFM-78
144
CFM-76
145
CFM-35
118
CFM-39
116
CFM-31
118
CFM-91
198
CFM-88
198
CFM-85
199
CFM-72
155
CFM-64
156
CFM-63
153
Airflow Setpoint
For setting the airflow setpoint on the FFU, please locate the section for the correct controller below (either ECMSC or BFC).
ECMSC SPEED CONTROLLER
7