DAMPER INSTALLATION
VAV DAMPER
MQ DAMPER
Damper Installation
Select the appropriate MQ/VAV Damper
required for the location based on the
diameter of the unit or zone duct.
The MQ/VAV damper should always be
installed in locations that are accessible
for inspection and removal if necessary.
In order to avoid additional noise in the
occupied space:
1. The MQ/VAV damper should be
installed at least 5 duct diameters
upstream of the active beam.
2. The MQ/VAV damper should be
used as a trimming damper and not
a balancing damper.
FLOOR MOUNTED ACTIVE BEAM
INSTALLATION & MOUNTING INSTRUCTIONS
8