Price Industries Limited HOLYOAKE RAP Series Manual Download Page 9

7

www.holyoakepureair.com   |   Room AIR PuRIfIeR - manual

Room AiR PuRifieR

Troubleshooting Tips

Low Air Velocity

1. Check pre-filter media (only with optional pre-filter); replace or clean as necessary
2. Adjust variable speed control for higher blower output.
3. Check power for proper voltage, amperage, and distribution frequency.
4. Replace HEPA filter if the velocity remains low.

High Air Velocity

1. Adjust variable speed control for lower blower output.

Motor Will Not Run

1. Check that motor has power at correct voltage.
2. Check that the speed controller has power.
3. Check control mode on speed controller and ensure setpoint is not 0%.
4. Check control harness between speed controller and motor

If experiencing further issues with unit, contact Price Holyoake help at: 

Australia

By Email:

 [email protected]

By Phone: 

1300 465 962 

New Zealand

By Email:

 [email protected]

By Phone: 

0800 114 810

TROUBLESHOOTING

Summary of Contents for HOLYOAKE RAP Series

Page 1: ...v001 Issue Date 12 08 21 2021 Price Industries Limited All rights reserved MANUAL INSTALLATION SERVICE Room Air Purifier RAP Series...

Page 2: ...ve These Instructions 1 Before You Start 1 Introduction 2 Installation Instructions Airflow Balancing 3 Service Instructions Filter Replacement 4 Motor Blower Field Replacement 4 Troubleshooting Troub...

Page 3: ...ent in the unit s external environment Before You Start Shipping Information Inspect all cartons and boxes for flaws and shipping damages If anything is discovered to be damaged contact the shipping c...

Page 4: ...ternal fan to draw air into the return through a HEPA filter and circulates the air back into the space through a grille With the fan continually running the air in your space is consistently filtered...

Page 5: ...with a slotted control screwdriver NOTE This potentiometer has voltage output for multi meter reading This is not required for setting airflow but can be utilised The potentiometers voltage range is...

Page 6: ...m requirements based on a 2 7m ceiling height can be seen below ACH Area m l s 2 48 72 66 99 97 146 132 198 163 245 197 296 3 32 72 44 99 65 146 88 198 108 243 132 297 4 24 72 33 99 48 144 66 198 81 2...

Page 7: ...cement Tools you will need to replace the motor blower assembly in the field 3 8 inch 9 5mm nut driver bit Wiring diagram located inside the control panel Recommended but not required Right angle atta...

Page 8: ...and 2 Rotate the blower into position so the top two holes line up Insert the bolts and hand tighten them in place 3 Use the 3 8 inch 9 5mm nut driver to tighten them 4 Plug the control and power wire...

Page 9: ...locity remains low High Air Velocity 1 Adjust variable speed control for lower blower output Motor Will Not Run 1 Check that motor has power at correct voltage 2 Check that the speed controller has po...

Page 10: ...Manual www holyoakepureair com Room Air Purifier RAP Unit Replacement Parts Filters Size WxHxT Quantity Description 610mm x 610mm x 102mm 1 Filter HEPA 99 97 610mm x 610mm x 25 4mm 1 Pre Filter MERV...

Page 11: ...9 www holyoakepureair com Room Air Purifier Manual Room Air Purifier NOTES...

Page 12: ...document contains the most current product information as of this printing For the most up to date product information please go to www holyoakepureair com 2021 Price Industries Limited All rights res...

Reviews: