www.holyoakepureair.com | Room AIR PuRIfIeR - manual
Room AiR PuRifieR
INSTALLATION INSTRUCTIONS
To install and utilise the RAP unit, it must be unboxed, the
castor wheels must be installed, and it must be placed in its
upright position. The unit can then be moved to its intended
zone near a wall with the front return panel facing out towards
the occupied space.
The RAP unit is designed to be powered with a 230V wall plug.
The wall plug should be locally sourced. Once plugged in, it
can be turned on, and the balancing procedure can begin.
Airflow Balancing
The RAP is furnished with an ECM motor, and an ECM speed
controller. The ECM speed controller has a manual adjustment
potentiometer that allows for modulation of airflow. This
potentiometer can be accessed and modulated with a slotted
control screwdriver.
NoTe:
This potentiometer has voltage output for multi-meter
reading. This is not required for setting airflow, but can be
utilised. The potentiometers voltage range is equivalent to the
following motor control range:
Measurement Tab Voltage
Motor Control
0 - 1 VDC
Off
1 - 4.5 VDC
0-100%
4.5 - 5 VDC
100%
The RAP is also furnished with an airflow adjustment sticker,
which allows for field airflow set point adjustment.
RAP LABeL, oN/off SWiTCH, AND WALL PLuG
THe RAP, PLuGGeD iN AND fACiNG
ToWARDS THe oCCuPieD ZoNe
BAS Common (
NoTe:
Same as 24 VAC Common)
BAS Input Type Voltage or Current - Shown set to voltage
Control Cable Jacks
BAS Positive Input (MAX +10 VDC)
24 VAC HOT Power
24 VAC Common (
NoTe:
Same as BAS Common)
NoTe:
BAS Common is connected to 24 VAC Common. If 24
VAC is earth grounded then BAS Common will be earth ground
as well. Polarity must be observed when connecting multiple
speed controllers and transformers.
eCm STANDARD SPeeD CoNTRoLLeR