Retransmission Output Type
Jumpers
4 to 20mA*
1 to 5V
J1
0 to 10V
J2
Table 3 - Jumper for retransmitter output type configuration
(*) In case of 4 to 20mA current retransmitter output, keep the jumper out of the
instrument or put it on only one pin of the connector, as shown in Figure 23.
Outputs 1 and 2 as alarm outputs
If output 1 or output 2 is required to operate as alarm, connect the optional
module in the connectors called MOD 1 and MOD 2, respectively. The output type
depends on the optional module installed in MOD 1 and MOD: SPST relay, the solid
state relay and the open collector voltage. The alarm output type and the optional
module code are listed in table 4.
Alarm Output Type
Optional Module Code
SPST Relay
MALRE - 20
Solid state relay
MALRS - 20
Open collector voltage
MSD - 20
Table 4 - Types of alarm output for outputs 1 and 2
Outputs 3 and 4 as alarm outputs
The outputs 3 and 4 work as alarm when one connects the optional module to
connectors MOD 3 and MOD 4, in this sequence. There are three types of alarm
outputs: SPDT relay, solid state relay and open collector voltage. The Alarm output
type and the optional module correspondence are shown in the table 5.
Alarm Output Type
Optional Module Code
SPDT Relay
MALRE - 20
Solid state relay
MALRS - 20
Open collector voltage
MSD - 20
Table 5 - Alarm output types for outputs 3 and 4