4.2 - Hardware Configuration
The software configuration level of input (level 2 - Input) must be
complemented by hardware configuration, through internal jumpers.
There are four places for installation of jumpers for channel 1: J5, J6, J7 and
J8; and four places for installation of jumpers for channel 2: J1, J2, J3 and J4. They
are placed in the CPU Board as shown in figure 22.
Figure 22 - Location of jumpers in CPU Board
Table 2 lists the jumpers that must be installed for each type of input. Verify
the input type required and place the jumpers as specified below. Make sure to install
only the jumpers required for the input.
Input type
Jumpers
Channel 2
Channel 1
Thermocouple
J1 J4 J5 J7
Voltage (0 to 55mV)
J1
J4
J5
J7
Voltage (0 to 5V)
J1
J4
J5
J7
Voltage (0 to 10V)*
J3
J6
2-wire or 3-wire RTD
J1
J2
J5
J8
Current (0 to 20mA)
J3
J4
J6
J7
Table 2 - Jumpers for input type configuration
(*) For 0 to 10V input, the second jumper supplied by the factory must be kept by the user
out of the instrument or placed on a conector as shown in Figure 23.