Start-Up Procedures
The display will flash once to confirm the
data has been saved.
•
To activate the stored parameter value,
press MODE twice to return to the STBY
mode.
If parameter 4 is adjusted for 140ºF target temperature at 0ºF outdoor air temperature
Table 3: Outdoor Air Temperature Reset (Example)
90
20
60
100
140
180
70
68
50
30
10
0
-10
86
B
o
ile
r
T
e
m
p
e
ra
tu
re
(
F
)
Outdoor Air Temperature ( F)
Parameter 4 Set Point
Graph 1: Outdoor Air Temperature Reset Curve (Example)
Outdoor
Boiler Target Temp.
Temperature
Based on Outdoor Temp.
0ºF or Lower
140ºF
23ºF
122ºF
40ºF
108ºF
68ºF or Higher
86ºF