87
19.0 Product Specifications
Boiler
Model
Fuel
Input
DOE
Heating Capacity
Net AHRI
Rating
DOE Seasonal
Efficiency AFUE
Shipping
Weight
Lbs / Kg
Solo 80
Natural
Propane
80,000
72,000
63,000
95%
103 / 47
Solo 110
Natural
Propane
110,000
99,000
86,000
95%
103 / 47
Solo 155
Natural
Propane
153,000
138,000
120,000
95%
118 / 53.5
Solo 175
Natural
Propane
170,000
154,000
134,000
95%
128 / 58
Solo 250
Natural
Propane
240,000
218,000
190,000
95%
140 / 63.5
Solo 299
Natural
Propane
299,000
272,000
237,000
95%
210 / 95
SECTION XIX PRODUCT SPECIFICATIONS
Boiler
Model
Fuel
Input
Output
Net AHRI
Rating
Combustion
Efficiency
Thermal
Efficiency
Shipping
Weight
Lbs / Kg
Solo 399
Natural
Propane
399,000
379,000
330,000
94.1%
95.1%
216 / 98
Note 1:
The heating capacity of the PRESTIGE Solo
80/110/155/175/250 is based on the test
requirements of the U.S. Department of
Energy.
Note 2:
The AHRI rating is based on a piping and
pick up allowance of 1.15. This allowance
should be sufficient for the standard radiation
requirements for a building load.
Note 3:
Based on the given AFUE the PRESTIGE
Solo 80/110/155/175/250 meets the energy
efficiency guidelines established by Energy
Star.
Note 4:
Input and output ratings are shown for sea
level applications. The PRESTIGE Solo
automatically derates the input at approxi-
mately 2% for every 1,000 Ft. of altitude. No
alterations to the boiler or burner system is
required.
Note 5:
PRESTIGE Solo 399 output rating is based
off of the thermal efficiency.
DOE