The above requirements allow also for use of a gas oven and grill but if there are other
gas burning appliances in the same room, consult a qualified engineer.
LOCATION
The appliance may be installed in a kitchen, Kitchen/diner or a bed sitting room, but not
in a room or space containing a bath or a shower.
The appliance must not be installed in a bed-sitting room of less than 20 m
3
.
The appliance is designed and approved for domestic use only and should not be
installed in a commercial, semi commercial or communal environment. Your product will
not be guaranteed if installed in any of the above environments and could affect any
third party or public liability insurances you may have.
VENTILATION REQUIREMENTS
The appliance should be installed into a room or space with an air supply in accordance
with BS 5440-2:2000.
For rooms with a volume of less than 5 m
3
- permanent ventilation of 100 cm
2
free area
will be required.
For rooms with a volume of between 5 m
3
and 10 m
3
a permanent ventilation of 50 cm
2
free area will be required unless the room has a door which opens directly to the outside
air in which case no permanent ventilation is required.
For rooms with a volume greater than 10 m
3
- no permanent ventilation is required.
NB. Regardless of room size, all rooms containing the appliance must have direct
access to the outside air via an openable window or equivalent.
Where there are other fuel burning appliances in the same room, BS 5440-2:2000 should
be consulted to determine the correct amount of free area ventilation requirements.