CommISSIoNING AND mAINTENANCE
dIsassemBlIng the Burner
prestIge solo 120
- Close the gas supply valve.
- Isolate the electric power supply.
- Open the front panel of the boiler.
- Disconnect the fan plugs (PWM & 230V), the ignition
cable, the gas valve control and the ignition electrode earth.
- Unscrew the three-piece connection of the gas pipe.
- Unscrew the fan’s 4 nuts and remove the fan, venturi and gas
valve assembly.
- Unscrew the 6 nuts of the chamber plate, using a ratchet
wrench.
- Lift up the chamber plate with the burner manifold, taking care
not to damage the insulation of the burner, which is inside of
the exchanger.
- Check the condition of the insulation and the seals and replace
them if needed, then put the burner back, following the above
procedure in reverse order.
BoIler maIntenance
prestIge solo 120
ACV recommends that you have your boiler
inspected, and cleaned, if needed, at least
once a year
.
Isolate the appliance before undertaking any work on it, even if you
are simply taking measurements and making adjustments.
- Check that the condensate trap is not clogged, fill it as required
and check for leaks.
- Check that the safety valves are in good working order.
- Bleed the whole system and refill the appliance if needed until it
reaches 1.5 bar.
In the case of repeated fills, contact your
installer. Why do we say this here?
- Check the boiler’s pressure in maximum power mode.
If this value is very different from the original setting, this
deviation may indicate an obstruction in the air intake ducts or
flue gas exhaust pipes, or that the exchanger is clogged.