PAC-M200-A Interface Module for PremiSys

®

 Air Products

3

Interface Module Replacement 

1) Shut off all power to the DOAS and connected outdoor unit.

2) Open Door #1 shown in Figure 1 (PAC-M200-A will be located here). 

3) Remove the cover on the PAC-M200-A.

4) Disconnect all wiring from the connectors and remove from the box. 

5) Remove the box and replace with new one.

6) Reroute all wires into the box and reconnect. Refer to the above wiring diagram, Figure 2 for correct connections.

7) Tighten all cable glands to secure wires.

8) Set DIP switches and address dials to the same settings as the box for replacement. Refer to Outdoor Reset    

    Function, page 8.

9) Replace cover on PAC-M200-A.

 

 

 

P.B.

C.B.

TB5

TB485

SW12 SW11

SW4

SW1

SW2

SW3

3

1

3

1

3

1

S (SHIELD)

1

6

CN60

M-NET

MODBUS

1

4

CN44

1

2

CN20

CNSV1

CNSV2

CNAC

CNLEV2

6

1

7

1

CN2M2

CN1

8

1

CNXB2

1

5

CNXB2

5

1

4

1

1

7

1

2

2

1

8

1

CNLEV

CN7V

CNXA2

CN2M

CN100

PAC-M200-A M-NET INTERFACE MODULE

 

+

G

-

4

3

2

1

TH22

TH23

TH25

LEV3a

LEV3b

M2

TB5

M-NET

CONNECTION

S

M1

TB485

TO MICROPROCESSOR

CONTROLLER

J25 BMS2 CONNECTION

SV11

SV10

POWER SUPPLY

AC208/230V 60HZ

M-NET WIRING

NOTE :1.Symbols used in wiring diagram above are,

           :Terminal

           (Heavy dotted line):Field wiring

           2.Use copper supply wires.

GROUND

FIELD WIRING

+ G

-

M2 S

M1

Figure 2. PAC-M200-A M-NET Wiring

© 2015 Mitsubishi Electric US, Inc.

Premi

Sys

Summary of Contents for PAC-M200-A

Page 1: ...ic work must be performed according to local regulation Improper electrical work may result in electric shock or fire PAC M200 A M NET Cable Specification Type Of cable Shielded wire 2 conductors CL3P...

Page 2: ...LTI System and PremiSys One CITY MULTI and One PremiSys 7 One CITY MULTI and Two PremiSys 7 Two CITY MULTI and One PremiSys 7 Outdoor Reset Function 8 Control Methods 9 Memo 10 11 Back Cover 12 Figure...

Page 3: ...e same settings as the box for replacement Refer to Outdoor Reset Function page 8 9 Replace cover on PAC M200 A P B C B TB5 TB485 SW12 SW11 SW4 SW1 SW2 SW3 3 1 3 1 3 1 S SHIELD 1 6 CN60 M NET MODBUS 1...

Page 4: ...d according to local regulation Improper electrical work may result in electric shock or fire PAC M100 A M NET Cable Specification Type Of cable Shielded wire 2 conductors CL3P CMP UL RoHS Conductor G...

Page 5: ...00 A 3 Disconnect the M NET wires from the TB5 terminal block 4 Unplug the Modbus wire from the CN2 connector Cut the plug off the end of the Modbus wire 5 Remove wires from box and then remove the bo...

Page 6: ...switches are all set to 0 when shipped from the factory Use these switches to set unit addresses and branch numbers as well P B C B TB5 TB485 SW12 SW11 SW4 SW1 SW2 SW3 3 1 3 1 3 1 S SHIELD 1 6 CN60 M...

Page 7: ...6 07 08 09 10 Two CITY MULTI Systems and one DOAS unit IDU 1 IDU 2 IDU 3 IDU 4 IDU 5 IDU 6 IDU 7 IDU 8 DOAS 1 Address 01 02 03 04 05 06 07 08 09 IDU 01 IDU 02 IDU 03 IDU 04 Address 01 Address 02 Addre...

Page 8: ...50F 50F 45F 45F 50F 55F 60F 65F 70F Outdoor Air Reset Function Factory Setting Supply Air Setpoint Outdoor Air Temperature Higher Lower Outdoor Reset Function Use DIP Switch SW3 and SW4 to Adjust Outd...

Page 9: ...roprocessor Supply Temp Set Point source to BMS 3 Set Microprocessor ON OFF control source to BMS 4 On central controller turn the system group to ON 5 On central controller turn the system group mode...

Page 10: ...PAC M200 A Interface Module for PremiSys Air Products 10 Memo 2015 Mitsubishi Electric US Inc PremiSys...

Page 11: ...PAC M200 A Interface Module for PremiSys Air Products 11 Memo 2015 Mitsubishi Electric US Inc PremiSys...

Page 12: ...15 Mitsubishi Electric US Inc PremiSys PAC M200 A Interface Module for PremiSys Air Products PA79D251H01 June 2015 12 PremiSys is a registered trademark of Greenheck Fan Corporation Used with permissi...

Reviews: