PAC-M200-A Interface Module for PremiSys

®

 Air Products

9

Control Methods

AUTO (Outdoor Reset) Control
System Supply Air will operate based on the Outdoor Reset Se

tti

ngs

Control method when the PremiSys is providing air into VFR Indoor Units

1. Leave the switches in factory default pos

iti

on on the interface control board

2. Set Microprocessor "Supply Temp Set Point" source to BMS
3. Set Microprocessor "ON/OFF" control source to BMS
4. On central controller, set the system group to ON
5. On central controller, set the system group mode to Auto 

The Set Temp. cannot be changed while opera

ti

ng in the auto mode

The current Set Temp. will be displayed
See VRF and PremiSys Integrated Control Func

ti

on below for descrip

ti

on 

of Mode prohibit

Note:
Mode prohibit can be ON or OFF

Controlling System Supply Air Temp from the central controller
System Supply Air Temp will operate based on the se

tti

ng in the central controller

Control method when air is directly into the space

1. Leave the Dip switches in factory se

tti

ng pos

iti

on on the interface control board

2. Set Microprocessor "Supply Temp Set Point" source to BMS
3. Set Microprocessor "ON/OFF" control source to BMS
4. On central controller, turn the system group to ON
5. On central controller, turn the system group mode to Cool or Heat

The Set Temp. for Cool or Heat mode will be the same
The unit will determine the Mode autom

ati

cally

6. Set the Set Temp. to a temperature that represents the average space Set Temp. 

served by this DOAS unit,, for example 72° F

Note:
Mode prohibit can be ON or OFF
See VRF and PremiSys Integrated Control Func

ti

on below

Recommended OFF when providing outside air directly to the space

VRF and PremiSys Integrated Control Func

ti

on

Overide the Supply Air Temperature setpoint in the above control setups
Best used when the air is supplied to the VRF indoor units

When all indoor units are in Cool mode and thermal ON,

the reheat will be turned o

ff 

and 55°

 

F air will be supplied

Under Prohibit Remote Controller Oper

ati

on, use the MODE prohibit switch

to ac

ti

vate and deac

ti

vate the this func

ti

on

Prohibit as shown, turns the func

ti

on OFF

Permit pos

iti

on turns the func

ti

on ON

Cool mode func

ti

on only

Cannot change se

tti

ng. Will display 

temperature based on reset chart above 

OR 

PremiSys

®

PremiSys

®

PremiSys

®

72

72

© 2015 Mitsubishi Electric US, Inc.

Premi

Sys

Summary of Contents for PAC-M200-A

Page 1: ...ic work must be performed according to local regulation Improper electrical work may result in electric shock or fire PAC M200 A M NET Cable Specification Type Of cable Shielded wire 2 conductors CL3P...

Page 2: ...LTI System and PremiSys One CITY MULTI and One PremiSys 7 One CITY MULTI and Two PremiSys 7 Two CITY MULTI and One PremiSys 7 Outdoor Reset Function 8 Control Methods 9 Memo 10 11 Back Cover 12 Figure...

Page 3: ...e same settings as the box for replacement Refer to Outdoor Reset Function page 8 9 Replace cover on PAC M200 A P B C B TB5 TB485 SW12 SW11 SW4 SW1 SW2 SW3 3 1 3 1 3 1 S SHIELD 1 6 CN60 M NET MODBUS 1...

Page 4: ...d according to local regulation Improper electrical work may result in electric shock or fire PAC M100 A M NET Cable Specification Type Of cable Shielded wire 2 conductors CL3P CMP UL RoHS Conductor G...

Page 5: ...00 A 3 Disconnect the M NET wires from the TB5 terminal block 4 Unplug the Modbus wire from the CN2 connector Cut the plug off the end of the Modbus wire 5 Remove wires from box and then remove the bo...

Page 6: ...switches are all set to 0 when shipped from the factory Use these switches to set unit addresses and branch numbers as well P B C B TB5 TB485 SW12 SW11 SW4 SW1 SW2 SW3 3 1 3 1 3 1 S SHIELD 1 6 CN60 M...

Page 7: ...6 07 08 09 10 Two CITY MULTI Systems and one DOAS unit IDU 1 IDU 2 IDU 3 IDU 4 IDU 5 IDU 6 IDU 7 IDU 8 DOAS 1 Address 01 02 03 04 05 06 07 08 09 IDU 01 IDU 02 IDU 03 IDU 04 Address 01 Address 02 Addre...

Page 8: ...50F 50F 45F 45F 50F 55F 60F 65F 70F Outdoor Air Reset Function Factory Setting Supply Air Setpoint Outdoor Air Temperature Higher Lower Outdoor Reset Function Use DIP Switch SW3 and SW4 to Adjust Outd...

Page 9: ...roprocessor Supply Temp Set Point source to BMS 3 Set Microprocessor ON OFF control source to BMS 4 On central controller turn the system group to ON 5 On central controller turn the system group mode...

Page 10: ...PAC M200 A Interface Module for PremiSys Air Products 10 Memo 2015 Mitsubishi Electric US Inc PremiSys...

Page 11: ...PAC M200 A Interface Module for PremiSys Air Products 11 Memo 2015 Mitsubishi Electric US Inc PremiSys...

Page 12: ...15 Mitsubishi Electric US Inc PremiSys PAC M200 A Interface Module for PremiSys Air Products PA79D251H01 June 2015 12 PremiSys is a registered trademark of Greenheck Fan Corporation Used with permissi...

Reviews: