MAINTENANCE

This maintenance schedule is only a guideline, determined by average conditions. Actual conditions will dictate 

the frequency of cleaning and/or replacement of lamps.  Do not touch the glass portion of the lamps with bare 

hands because oils from the hands can cause “hot spots” which reduce lamp life.  Handle either by the end caps or 

use a soft cloth.  If  you accidentally touch a lamp, clean it using a soft cloth dampened with rubbing alcohol.

CLEANING THE GERMICIDAL LAMP

 

- Recommended interval: 12 months

1. Disconnect power to the unit.
2. Unplug mid-cord connectors by pressing the lock release (marked “PRESS” on the connector.)

    Remove two thumb nuts holding moisture resistant lamp socket to mounting plate and carefully remove the

    lamp socket with lamp from the mounting plate. Repeat this step for the other three lamps.
3. Use a soft cloth moistened with rubbing alcohol to wipe down each lamp.  If there is a  large build-up of dust 

    particles, you may wish to use a can of air first.  Do not touch the glass portion of the lamps with bare hands.
4. Carefully slide the moisture lamp socket with lamp through the mounting plate into duct fitting over the 

    mounting studs and secure using the two thumb nuts. (Photo A)
5. Reconnect the mid-cord connector. Be sure to line up arrows on the connector. (Photo B)

    Repeat this step for the other three lamps.
6. Supply power to the unit.

REPLACING THE LAMP

 

-  Recommended interval: 24 months                  

Replacement lamps are available through your HVAC contractor.  
Follow above procedure except #3 where you replace the lamps instead of cleaning them. 

(Note: standard off-the-shelf lamps are not compatible with this unit. Use of improper lamps will void warranty.)

 

  LSK200-16 

 

 

         LSK200-12   

 

       

LAMP KITS FOR MUV7-200QR

#LSK200-16

  UVC lamp service kit with two (4) 16” UV lamps - 36-Watt each.

#LSK200-12

  UVC lamp service kit with two (4) 12” UV lamps - 24-Watt each.

For Technical Support Call (800)982-1840    www.premieroneproducts.com   ©2020 

Summary of Contents for MUV7-200QR

Page 1: ...nt l installation ou le service 3 Ne pas regarder la lampe directement avec les yeux Si n cessaire de le faire veuillez porter les lunettes de soleil contre les rayons U V IMPORTANT SAFETY INSTRUCTION...

Page 2: ...install the UVC lamps where there is a straight line of sight of the lamps through a vent When choosing a location to mount the lamps make certain no UV light is visible to the consumer 3 Using a 1 1...

Page 3: ...he combined microwatts to be sufficient for the air volume Lamps should be mounted with as much distance upstream and downstream as possible Example in a ten 10 foot duct lamps should be mounted at fi...

Page 4: ...ire to neutral green wire to ground For 240V wiring install 5 amp inline fuses to both legs of power then connect the black wire to L1 white wire to L2 green wire to ground Be sure power cord is secur...

Page 5: ...lamp connectors are fastened securely 3 If the LED still does not light replace lamp s 4 If still not operating replace ballast Note Standard off the shelf lamps are not compatible with this unit Use...

Page 6: ...ing alcohol to wipe down each lamp If there is a large build up of dust particles you may wish to use a can of air first Do not touch the glass portion of the lamps with bare hands 4 Carefully slide t...

Page 7: ...of the duration of an implied warranty so the above limitations or exclusions may not apply to the customer This Limited Warranty gives the customer specific legal rights and the customer may also hav...