Illustration #1 Ballast 1 & 2,
(2 lamps per ballast)
For Technical Support Call (800)982-1840 www.premieroneproducts.com ©2020
WIRING/FUSE
The multivoltage ballast is self-adjusting and operates with voltages from 120 - 240 VAC. For 120V wiring
connect the black wire to L1, white wire to neutral, green wire to ground. For 240V wiring install 5 amp inline
fuses to both legs of power, then connect the black wire to L1, white wire to L2, green wire to ground. Be sure
power cord is secured with included strain relief connector.
It is recommended you interlock with the system blower or install a blower door safety switch so the
unit powers off when the system is serviced. Connect in accordance with local wiring codes.
CORRECT WIRING FOR
FOUR
LAMP OPERATION.