ProtEX-MAX PD8-6001 Explosion-Proof Feet & Inches Meter Instruction Manual
46
Display
Parameter
Action/Setting
Calib
Calibrate
Calibrate 4-20 mA output
(internal reference source
used for scaling the output)
4 mA
4 mA output
Enter mA output value read by
milliamp meter with at least
0.001 mA resolution
20 mA
20 mA
output
Enter mA output value read by
milliamp meter with at least
0.001 mA resolution
user
User I/O
Assign function keys and
digital I/O
F1
*
F1 function
key
*Assign F1-F4 function key
Ack
Acknowledg
e
Acknowledge relays
reset
Reset
Enter
Reset
menu
Rst Hi
Reset Max
Reset Maximum
Rst Lo
Reset Min
Reset Minimum
Rst HL
Reset Max-
Min
Reset Maximum & Minimum
relay
Relay
Relay menu
Set 1
*
Set Points
1-8
Set Points 1-8
Rly d
Relay
Disable
Relay Disable (all relays)
Rly e
Relay
Enable
Relay Enable (all relays)
O Hold
Output Hold
Output Hold (all relays)
d Hold
Display
Hold
Display Hold (while held low)
Ln1 Hi
Line 1 High
Max on line 1
Ln1 lo
Line 1 Low
Min on line 1
Ln1 Hl
Line 1
High/Low
Max/min line 1
Display
Parameter
Action/Setting
Ln2 Hi
Line 2 High
Max on line 2
Ln2 lo
Line 2 Low
Min on line 2
Ln2 Hl
Line 2
High/Low
Max/min line 2
F On 1
*
Force On
Relay 1
*Force relay 1-4 on
Contrl
Control
Control Menu
disabl
Disable
Disable
dI I
Digital input
1
Assign digital input 1
– 4
dO 1
Digital
output 1
Assign digital output 1
– 4
ICal
Internal
source
calibration
Enter internal source
calibration (used for scaling
the meter without a signal
source)
C CAL
Current
calibration
Calibrate 4-20 mA current
input (internal reference
source used for scaling the
input)
C lo
Current low
Calibrate low current input
(e.g. 4 mA)
C Hi
Current
high
Calibrate high current input
(e.g. 20 mA)
v CAL
Voltage
calibration
Calibrate voltage input
v Lo
Voltage low
Calibrate low voltage input
(e.g. 0 V)
v Hi
Voltage
high
Calibrate high voltage input
(e.g. 10 V)
Diag
Diagnostics
Display parameter settings
LED t
LED test
Test all LEDs
Info
Information
Display software and S/N
information
Erase
Erase
Erase MeterView Pro software
stored in meter’s memory