ProtEX-MAX PD8-6001 Explosion-Proof Feet & Inches Meter Instruction Manual
45
Advanced Features Menu
To simplify the setup process, functions not needed for most applications are located in the
Advanced
Features
menu.
Press and hold the Menu button for three seconds to access the advanced features of the meter.
Advanced Features Menu & Display Messages
The following table shows the functions and messages of the
Advanced Features
menu in the order they appear in
the menu.
Display
Parameter
Action/Setting
filtEr
Filter
Set noise filter value
bypASs
Bypass
Set filter bypass value
Round
Round
Set the rounding value for
display variables
seriAl
Serial
Set serial communication
parameters
SlavId
Slave ID
Set slave ID or meter address
baud
Baud rate
Select baud rate
Tr dLY
Transmit
delay
Set transmit delay for serial
communication
Parity
Parity
Select parity
Even, Odd, or None with 1 or 2
stop bits
t-byt
Time byte
Set byte-to-byte timeout
SelEct
Select
Enter the Select menu
(function, cutoff, out)
Functn
Signal input
conditioning
Select linear, square root,
programmable exponent, or
round horizontal tank function
Pv 1
PV1
Select PV1 number of
linearization points
Linear
Linear
Set meter for linear function
and select number of
linearization points
No PtS
Number of
points
Set PV1 for 2 to 32-point
linearization
Set PV2 for 2 to 8-point
linearization
Display
Parameter
Action/Setting
Pv 2
PV2
Select PV2 number of
linearization points
rht
Round
horizontal
tank
Set meter for round horizontal
tank volume calculation
Inch
Dimension
Calculate volume in gallons
cm
Dimension
Calculate volume in liters
diamr
Diameter
Enter the tank’s diameter in
inches
Length
Length
Enter the tank’s length in
inches
Cutoff
Cutoff
Program Low Flow Cutoff
Value for PV 1
aoutPr
Analog
Output
Program
Enter
Analog Output
Programmable
parameters
menu
Source
Source
Select source for the 4-20 mA
output
O-rang
Overrange
Program mA output for display
overrange
u-rang
Underrange
Program mA output for display
underrange
break
Break
Set input break condition
operation
mAx
Maximum
Program maximum mA output
allowed
min
Minimum
Program minimum mA output
allowed