PD6210 Analog Input Batch Controller Instruction Manual
6
Specifications
Except where noted all specifications apply to operation at +25°C.
General
Display
Line 1: 0.6" (15 mm) high, red LEDs
Line 2: 0.46" (12 mm) high, red LEDs
6 digits: each (-99999 to 999999), with lead
zero blanking.
Default
Display
Assignment
The Upper display shows batch total. The
Lower display shows rate with alternating
units, and can be switched to show grand
total, batch count, or preset with the STOP
key.
Custom
Display
Assignment
The Upper and Lower displays may be
assigned to rate, total, grand total, batch
count, preset, set points, units (lower display
only), alternating R & T, R & GT, preset &
rate, max & min, or a Modbus display
register. Any rate/total/grand total display
may be programmed to alternate with a
custom unit or tag.
Alternating
Display
Displays alternate every 10 seconds when
display is selected or the batch is paused.
Display
Intensity
Eight user selectable intensity levels
Display
Update Rate
5/second (200 ms)
Overrange
Display flashes
999999
Underrange
Display flashes
-99999
Front Panel
NEMA 4X, IP65
Programming
Methods
Four front panel buttons, digital inputs, or
PC and MeterView Pro software.
Noise Filter
Programmable from 2 to 199 (0 will disable
filter)
Filter Bypass
Programmable from 0.1 to 99.9% of
calibrated span
Recalibration
All ranges are calibrated at the factory.
Recalibration is recommended at least every
12 months.
Max/Min
Display
Max/min readings reached by the process
are stored until reset by the user or until
power to the controller is cycled.
Password
Three programmable passwords restrict
modification of programmed settings and
two prevent resetting the totals.
Pass 1: Allows use of function keys and
digital inputs
Pass 2: Allows use of function keys, digital
inputs and editing set/reset points
Pass 3: Restricts all programming, function
keys, and digital inputs.
Total Password: Prevents resetting the total
manually
Gtotal Password: Prevents resetting the
grand total manually
Non-Volatile
Memory
All programmed settings are stored in non-
volatile memory for a minimum of ten years
if power is lost.
Power
Options
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W
max or 12-24 VDC
10%, 15 W max
Powered over USB for configuration only
Fuse
Required external fuse: UL Recognized, 5 A
max, slow blow; up to 6 controllers may
share one 5 A fuse
Isolated
Transmitter
Power Supply
Terminals P+ & P-: 24 VDC
10%. 12-24 VDC
powered models selectable for 24, 10, or 5VDC
supply (internal jumper J4).
85-265 VAC models rated @ 200 mA max, 12-
24 VDC powered models rated @ 100 mA max,
@ 50 mA max for 5 or 10 VDC supply.
Normal Mode
Rejection
Greater than 60 dB at 50/60 Hz
Isolation
4 kV input/output-to-power line
500 V input-to-output or output-to-P+ supply
Overvoltage
Category
Installation Overvoltage Category II:
Local level with smaller transient
overvoltages than Installation Overvoltage
Category III.
Environmental
Operating temperature range: -40 to 65°C
Storage temperature range: -40 to 85°C
Relative humidity: 0 to 90% non-condensing
Connections
Removable screw terminal blocks accept 12
to 22 AWG wire, RJ45 for external relays,
digital I/O, and serial communication
adapters.
Enclosure
1/8 DIN, high impact plastic, UL 94V-0,
color: black
Mounting
1/8 DIN panel cutout required:
3.622" x 1.772" (92 mm x 45 mm)
Two panel mounting bracket assemblies are
provided.
Tightening
Torque
Screw terminal connectors: 5 lb-in (0.56 Nm)
Overall
Dimensions
4.68" x 2.45" x 5.64" (119 mm x 62 mm x
143 mm)
(W x H x D)
Weight
9.5 oz (269 g)
Warranty
3 years parts & labor
Process Input
Inputs
Field selectable:
0-20, 4-20 mA,
10 V (0-5, 1-5, 0-10 V),
Modbus PV (Slave)
Accuracy
±0.03% of calibrated span ±1 count,
square root & programmable exponent
accuracy range:
10-100% of calibrated span
Temperature
Drift
0.005% of calibrated span/
C max from 0 to
65
C ambient,
0.01% of calibrated span/
C max from -40 to
0
C ambient
Signal Input
Conditioning
Linear, square root, or programmable
exponent
Multi-Point
Linearization
2 to 32 points