background image

 

Helios Large Display Analog Input Batch Controller Instruction Manual 

PD2-6210

 

 

56 

 

 

Internal Source Calibration (

ICAL

The meter is factory calibrated prior to shipment to read in milliamps and 

volts depending on the input selection. The calibration equipment is 

certified to NIST standards. 

 

The use of calibrated signal sources is necessary to calibrate the internal source of the meter. The 

meter’s internal source is what allows the user to scale the meter without applying a signal. 
Check calibration of the meter at least every 12 months. Each input must be recalibrated separately. 

Notes: 

1.  If meter is in operation and it is intended to accept only one input type (e.g. 4-20 mA), 

recalibration of other input is not necessary. 

2.  Allow the meter to warm up for at least 15 minutes before performing the internal source 

calibration procedure. 

The Internal calibration menu is part of the Advanced Features menu.  
1.  Press and hold the Menu button for three seconds to access the advanced features of the meter. 

2.  Press the Up

 

arrow button to scroll to the 

Internal calibration

 menu (

ICAL

) and press Enter. 

3.  The meter displays either current calibration (

C CAL

) or voltage calibration (

v CAL

), according to the 

input setup. Press Enter

 

to start the calibration process. 

Example of Internal Calibration for current input: 

4.  The meter displays 

low

 input current message (

C lo

). Apply the low input signal and press Enter. The 

display flashes for a moment while the meter is accepting the low input signal. 

5.  After the display stops flashing, a number is displayed with the leftmost digit brighter than the rest. 

The bright digit is the active digit that can be changed by pressing the Up

 

arrow button. Press the 

Right

 

arrow button to move to the next digit. 

6.  Set the display value to correspond to the input signal being calibrated, typically 4.000 mA. 

7.  The display moves to the 

high

 input 

calibration (

C Hi

). Apply the high 

input signal and press Enter. 

8.  Set the display for the high input 

calibration, in the same way as it 

was set for the low input calibration, 

typically 20.000 mA. 

The graphic shows the calibration of the 

current input. The voltage input is 

calibrated in a similar way. 

Tips: 

  Low and high input signals can 

be any valid values within the range of the meter. 

  Observe minimum input span requirements between input 1 and input 2. 

  Low input should be less than high input signal. 

Error Message (

Error

An error message indicates that the calibration or scaling 

process was not successful. 

The error message might be caused by any of the following 

conditions: 

1.  Input signal is not connected to the proper 

terminals, or it is connected backwards. 

2.  Wrong signal selection in 

Setup

 menu. 

3.  Minimum input span requirements not maintained. 

Minimum Input Span 

The minimum input span is the minimum 

difference between input 1 and input 2 

signals required to complete the calibration 

or scaling of the meter. 

Input Range  Input 1 & Input 2 Span 
4-20 mA 

0.15 mA 

10 VDC 

0.01 VDC 

 

 

www.calcert.com

[email protected]

1.888.610.7664

0

5

10

15

20

25

30

Summary of Contents for PD2-6210

Page 1: ...lti Stage Batch Control up to 4 Relays 0 20 mA 4 20 mA 0 5 V 1 5 V and 10 V Inputs Input Power Options Include 85 265 VAC or 12 24 VDC Isolated 24 VDC Transmitter Power Supply Start Pause Stop Change...

Page 2: ...ury or property loss Anyone using this product for such applications does so at their own risk Precision Digital Corporation shall not be held liable for damages resulting from such improper use Limit...

Page 3: ...lays 40 Programming Set and Reset Points 41 Setting Fail Safe Operation 41 Programming Time Delay 41 Relay Action for Loss of 4 20 mA Input Loop Break 41 Relay and Alarm Operation Diagrams 42 High Ala...

Page 4: ...s large 1 8 superluminous inch LED digits which can be read in sunlight from up to 100 feet away It is housed in a water resistant field mountable NEMA 4X IP65 rated enclosure for convenient indoor an...

Page 5: ...s paused Programming Methods Four programming buttons digital inputs PC and MeterView Pro software or Modbus registers Noise Filter Programmable from 2 to 199 0 will disable filter Filter Bypass Progr...

Page 6: ...10 100 of calibrated span Temperature Drift 0 005 of calibrated span C max from 0 to 65 C ambient 0 01 of calibrated span C max from 40 to 0 C ambient Signal Input Conditioning Linear square root prog...

Page 7: ...ds see page 17 for details Deadband 0 100 of span user programmable 1 Alarms are active only when the batch is running High or Low Alarm User may program any alarm for high or low trip point Unused al...

Page 8: ...Receive RX Modbus RTU Serial Communications Slave Id 1 247 Controller address Baud Rate 300 19 200 bps Transmit Time Delay Programmable between 0 and 199 ms Data 8 bit 1 start bit 1 or 2 stop bits Pa...

Page 9: ...SA Canada UL 508 Industrial Control Equipment United States C22 2 No 142 Canadian National Standard UL File Number E160849 Front Panel UL Type 4X NEMA 4X IP65 Low Voltage Directive EN 61010 1 2010 Saf...

Page 10: ...nockout holes located on the bottom of the controller There are a total of four pre drilled conduit entry holes located at the bottom of the controller If the need to drill additional holes arises mak...

Page 11: ...the wall 2 Using a drill bit slightly smaller than the girth of the mounting screws pre drill holes at the mounting locations previously marked 3 Insert mounting screws into the four mounting holes an...

Page 12: ...ctions 1 Secure the mounting plates to the top and bottom for vertical pipes or left and right for horizontal pipes of the reverse side of the meter enclosure using the provided fasteners Do not overt...

Page 13: ...ter of the connections board see diagram below 4 Flip this switch into the appropriate position for the required transmitter excitation Figure 6 Transmitter Supply Voltage Selection Connections All co...

Page 14: ...d to the left of the power terminal block Doing so will disable the onboard digital I O RS 485 serial communications and M Link functionality Figure 7 Connector Labeling for Fully Loaded PD2 6210 Powe...

Page 15: ...s to set up for current and voltage inputs Setup and programming is performed through the front panel buttons Figure 9 Transmitters Powered by Internal Supply Figure 10 Transmitter Powered by Ext Supp...

Page 16: ...5 for additional information Relay Connections Relay connections are made to two six terminal connectors labeled RELAY1 RELAY4 on Figure 7 Each relay s C terminal is common only to the normally open...

Page 17: ...each amp through closed contacts Notes 1 Use capacitors rated for 250 VAC 2 RC networks may affect load release time of solenoid loads Check to confirm proper operation 3 Install the RC network at th...

Page 18: ...Figure 16 shows the connection of several meters to a PC using a PDA7485 RS 232 to RS 422 485 converter in an RS 485 network When using more than one meter in a multi drop mode each meter must be pro...

Page 19: ...nections Figure 17 details the wiring connections from the RS 485 connector to an RS 422 485 serial converter such as the PDA7485 or PDA8485 for a four wire network Three Wire Connection In order to w...

Page 20: ...r block and the 5 VDC block Digital output connections are made by wiring from the appropriate digital output block to the grounding terminal block Figure 19 Digital Input and Output Connections F4 Di...

Page 21: ...rlock Relay Feature As the name implies the interlock relay feature reassigns one or more alarm control relays for use as interlock relay s Interlock contact s are wired to digital input s and trigger...

Page 22: ...the input selection The calibration equipment is certified to NIST standards Overview There are no jumpers to set for the meter input selection Setup and programming are done through the programming b...

Page 23: ...indicator Note F4 F8 are digital inputs Total overflow indicator M Flashing Manual control of flashing relays M flashing alone indicates manual analog output Indicators flash every 10 seconds Press th...

Page 24: ...the drive labeled MAINSTAL 3 Double click on the file named MAStart The program will open a few windows and install two programs on your computer Simply follow the onscreen instructions until you see...

Page 25: ...batch process is running A 4 20 mA output option is also available for retransmitting the process variable analog signal Default Batch Control Operation The following describes the operation of the t...

Page 26: ...with one relay for control then one would set the assignment of relay 2 assign2 to off rate or grand total The following pages show an illustration of how the above settings control the batch operati...

Page 27: ...PD2 6210 Helios Large Display Analog Input Batch Controller Instruction Manual 27 www calcert com sales calcert com 1 888 610 7664 0 5 10 15 20 25 30...

Page 28: ...ignal or program input 2 value up to 32 points Dis 2 Display 2 Program display 2 value up to 32 points Error Error Error calibration not successful check signal or programmed value T tb Total time bas...

Page 29: ...lays 2 4 setup FaiLSF Fail safe Enter Fail safe menu FLS 1 Fail safe 1 Set relay 1 fail safe operation on On Enable fail safe operation off Off Disable fail safe operation FLS 2 Fail safe 2 Set relays...

Page 30: ...ter to set meter for automatic operation mAn Manual Press Enter to manually control relays or analog output operation pass Password Enter the Password menu Pass 1 Password 1 Set or enter Password 1 Pa...

Page 31: ...nter F3 The display moves to the next menu every time a setting is accepted by pressing Enter F3 Setting Numeric Values The numeric values are set using the Right and Up arrow buttons Press Right arro...

Page 32: ...apable of accepting any signal from 10 to 10 VDC Select voltage input to accept 0 5 1 5 0 10 or 10 VDC signals Setting the Totalizer and Batching Features total To simply not display the total select...

Page 33: ...6 9 g p P 7 7 H H q q 8 8 h h r r 9 9 I I s S A A I i t t Degree b b j J u u Space Notes Degree symbol represented by if programming with MeterView Pro The letters m and w use two 7 segment LEDs each...

Page 34: ...rsion factor 5 Total reset mode for total grand total Note The Scale and Calibrate functions are exclusive of each other The meter uses the last function programmed Only one of these methods can be em...

Page 35: ...can be employed at a time The Scale and Calibrate functions can use up to 32 points default is 2 The number of points should be set in Scale and Calibrate accordingly under the Number of Points nopts...

Page 36: ...intained 4 Input 1 signal inadvertently applied to calibrate input 2 Minimum Input Span The minimum input span is the minimum difference between input 1 and input 2 signals required to complete the ca...

Page 37: ...Time Base The time base is the amount of time over which the rate parameter should accrue For example if the rate was ten and the time base was in minutes then the total would increase by ten every o...

Page 38: ...grand total and units 4 Display max and min values 5 Display Modbus input 6 Off no display 7 Display rate units 8 Display rate 9 Display total 10 Display grand total 11 Toggle rate and total 12 Toggle...

Page 39: ...ted for a user specified time g Off relay state controlled by Interlock feature 3 Set and reset points 4 Fail safe operation a On enabled b Off disabled 5 Time delay a On delay 0 999 9 seconds b Off d...

Page 40: ...is in other applications 4 Automatic manual reset when not in a batch process non latching 5 Latching manual reset only when not in a batch process 6 Latching with Clear manual reset only when not in...

Page 41: ...n to enable or select off to disable fail safe operation Failsafe mode should not be used on batch relays assigned to total Programming Time Delay The On and Off time delays may be programmed for each...

Page 42: ...n non alarm condition In case of power failure relay will go to alarm state Low Alarm with Fail Safe Operation Set Reset Note Relay coil is energized in non alarm condition In case of power failure re...

Page 43: ...on alarm condition 3 Ignore Processed as a low signal condition Time Delay Operation The following graphs show the operation of the time delay function When the signal crosses the set point the On tim...

Page 44: ...to their programmed states when the batch process is started Grand total alarm relays will initialize to their programmed state at controller power up Fail Safe Operation The following table indicates...

Page 45: ...e set up as interlock relays To set up the relays for the interlock feature 1 Access the Setup Relay Action menu and set the action to off 2 In the Advanced features User menu program any of the digit...

Page 46: ...Analog Output Aout The 4 20 mA analog output can be scaled to provide a 4 20 mA signal for any display range selected No equipment is needed to scale the analog output simply program the display value...

Page 47: ...events resetting the total manually Gtotal Prevents resetting the grand total manually Protecting or Locking the Meter Enter the Password menu and program a six digit password For instructions on how...

Page 48: ...word menu and enter the correct password twice as shown below The meter is now unprotected until a new password is entered If the correct six digit password is entered the meter displays the message u...

Page 49: ...up at the factory for 2 point linear calibration The number of points for multi point calibration scaling is set up in the Advanced Features menu Up to 32 linearization points may be selected See page...

Page 50: ...ding value for display variables seriAl Serial Set serial communication parameters SlaveId Slave ID Set slave ID or meter address baud Baud rate Select baud rate Tr dLY Transmit delay Set transmit del...

Page 51: ...mA output value read by milliamp meter with at least 0 001 mA resolution user User I O Assign function keys and digital I O F1 F1 function key Assign F1 function key F2 F2 function key Assign F2 funct...

Page 52: ...ted See examples below Modbus RTU Serial Communications serial The meter is equipped with serial communications capability as a standard feature using Modbus RTU Serial Communication Protocol The mete...

Page 53: ...Square Root Linearization Square The square root function can be used to linearize the signal from a differential pressure transmitter and display flow rate in engineering units Programmable Exponent...

Page 54: ...te Calibrate the internal 4 20 mA source reference used to scale the 4 20 mA output Analog Output Source The source for generating the 4 20 mA output may be assigned to the rate process variable total...

Page 55: ...isplay values on line 2 Ln2 gt Display the grand total on line 2 Ln2 bc Display the batch count on line 2 Contrl Directly access the control menu Display Description disabl Disable the selected functi...

Page 56: ...lay flashes for a moment while the meter is accepting the low input signal 5 After the display stops flashing a number is displayed with the leftmost digit brighter than the rest The bright digit is t...

Page 57: ...s Up arrow button and scroll to Information menu Info 3 Press Enter to access the software number SFT and version UER information Write down the information as it is displayed Continue pressing Enter...

Page 58: ...Ddd ddd 3 places Total decimal point Ddddd d 1 place Gr total decimal point Dddddd 0 places Cutoff value CutofF 0 000 disabled Display line 1 Line 1 Rate Process Display line 2 Line 2 Total value Disp...

Page 59: ...Off Fail safe relay 4 Fls 4 Off Display 1 analog out Dis 1 4 000 Output 1 value Out 1 4 000 mA Display 2 analog out Dis 2 20 000 Output 2 value Out 2 20 000 mA Source analog output Source Rate process...

Page 60: ...not respond to input changes reading a fixed number Check Display assignment it might be displaying max min or set point Display alternates between Hi and a number Lo and a number Press Menu to exit...

Reviews: