ProtEX-MAX PD8-6210 Explosion-Proof Analog Input Batch Controller
Instruction Manual
20
Digital Input (F4)
Function
Start/Stop batch, remote operation of
front-panel buttons, acknowledge/reset
relays, reset max/min values. See
Keys & Digital I/O Available Settings
for a complete list of capabilities.
Contacts
3.3 VDC on contact. Connect normally
open contacts across F4 to COM.
Logic Levels
Logic High: 3 to 5 VDC
Logic Low: 0 to 1.25 VDC
Digital Inputs & Outputs
Function
Terminals provided for remote operation of
all four programming / operation buttons.
Other uses include acknowledge/reset
relays and reset max/min values. See
Function Keys & Digital I/O Available
Settings
for a complete list of
capabilities.
Channels
4 digital inputs & 4 digital outputs
Digital Input
Logic High
3 to 5 VDC
Digital Input
Logic Low
0 to 1.25 VDC
Digital Output
Logic High
3.1 to 3.3 VDC
Digital Output
Logic Low
0 to 0.4 VDC
Source
Current
10 mA maximum output current
Sink Current
1.5 mA minimum input current
+5 V Terminal
To be used as pull-up for digital inputs only.
Connect normally open push buttons
5 V & DI 1-4.
•
DO NOT
use +5 V terminal to power external
devices.
MeterView Pro Software
Availability
Download directly from controller or from
www.predig.com/download_software
System
Requirements
Microsoft
®
Windows
®
XP/Vista/7/8/10
Communications
USB 2.0 (for programming only)
(USB A Male to Micro-B Cable)
RS-485 to USB converter
(programming, monitoring, batch
control, and data logging)
Configuration
Configure controllers one at a time
Power
USB port provides power to the
controller for configuration only.
DO NOT apply AC or DC power to the
controller while the USB port is in use.
Batch Control
Use MeterView Pro to control the
batch, change the preset, reset totals,
and test the relays.
Data Logging
Use MeterView Pro for data logging of
the batch process.