ProtEX-MAX PD8-6000 Explosion-Proof Process Meter
Instruction Manual
51
Advanced Features Menu & Display Messages
Display
Parameter
Action/Setting
ICal
Internal source
calibration
Enter internal source
calibration (used for
scaling the meter without a
signal source)
C CAL
Current
calibration
Calibrate 4-20 mA current
input (internal reference
source used for scaling the
input)
C lo
Current low
Calibrate low current input
(e.g. 4 mA)
C Hi
Current high
Calibrate high current input
(e.g. 20 mA)
V CAL
Voltage
calibration
Calibrate voltage input
V Lo
Voltage low
Calibrate low voltage input
(e.g. 0 V)
V Hi
Voltage high
Calibrate high voltage input
(e.g. 10 V)
Diag
Diagnostics
Display parameter settings
LED t
LED test
Test all LEDs
(press menu to exit test)
Info
Information
Display software number
and version
Erase
Erase
Erase MeterView Pro SW
stored in meter’s memory
Noise Filter (
filter
)
The noise filter is available for unusually noisy signals
that cause an unstable process variable display. The
noise filter averages the input signal over a certain
period. The filter level determines the length of time
over which the signal is averaged. The filter level can
be set between 2 and 199. The higher the filter level,
the longer the averaging time and so the longer it
takes the display to settle to its final value. Setting the
filter level to zero disables the filter function.
Noise Filter Bypass (
bypass
)
The noise filter bypass changes the behavior of the
meter so that small variations in the signal are filtered
out but large abrupt changes in the input signal are
displayed immediately. The bypass value determines
the minimum amount of signal change to be displayed
immediately. All signal changes smaller than the
bypass value are filtered or averaged by the meter.
The noise filter bypass may be set between 0.1 and
99.9% of full scale.
Rounding Feature (
round
)
The rounding feature is used to give the user a
steadier display with fluctuating signals. Rounding is
used in addition to the filter function.
Rounding causes the display to round to the nearest
value according to the rounding selected. See
examples below:
Rounding
Selection
Actual
Value
Display
Value
Actual
Value
Display
Value
1
12.022
12.022
12.023
12.023
5
12.022
12.020
12.023
12.025
10
12.024
12.020
12.025
12.030
Modbus
®
RTU Serial
Communications (
serial
)
The meter is equipped with serial communications
capability as a standard feature using Modbus
®
RTU
Serial Communication Protocol.
The meter may be connected to a PC for initial
configuration via the on-board USB connection. For
ongoing digital communications with a computer or
other data terminal equipment, use the RS-485
connection.
•
DO NOT
connect any equipment to the RJ45
M-LINK connector. Otherwise damage will occur
to the equipment and the meter.
•
DO NOT
disconnect the RJ45 connector located
to the left of the power terminal block. Doing so
will disable the on-board digital I/O, and the
RS-485 serial communications.
Notes:
1.
Refer to the ProtEX-MAX Modbus
®
Register Tables
located at
2.
Changes made to the Serial menu are initialized after
the menu key is pressed or after navigating through the
remainder of the serial parameters (i.e. pass the t-byte
parameter).
When using more than one meter in a multi-drop
mode, each meter must be provided with its own
unique address. The meter address (Slave ID) may
be programmed between 1 and 247. The transmit
delay may be set between 0 and 199 ms. The parity
can be set to even, odd, or none with 1 or 2 stop bits.