PD6928 Loop-Powered Flow Rate/Totalizer
Instruction Manual
17
4-20 mA Transmitter Output
Accuracy
±
0.05% FS
±
0.001mA
Output
Source
Rate, total, re-transmit;
reverse scaling
allowed
Scaling
Range
1.00 to 23.0 mA
Disable
High impedance state, less than 1 mA
Calibration
Factory calibrated 4.00 to 20.00 mA
Underrange
1.0 mA, 3.5 mA, or 3.8 mA
(If input < 3.5 mA); or Off;
user selectable
Overrange
20.5 mA, 20.8 mA, or 23.0 mA
(If input > 20.5 mA); or disable overrange;
user selectable
Isolation
500 V input-to-output
Temperature
Drift
0.5 µA/°C max from -40 to 75°C ambient
External Loop
Power Supply
7.0 VDC to 30.0 VDC maximum
Output Loop
Resistance
10-
750 Ω @ 24 VDC; 10-1100 Ω @ 30 VDC
On-Board Digital Input
Function
Remote operation of front-panel buttons,
acknowledge/reset relays, reset total, reset
max/min values, etc. See User section of
on page
for a complete list of capabilities.
Contacts
2.1 VDC on contact. Connect normally open
contacts across DI+ and DI-
Logic Levels
Logic High: 2.4 to 30 VDC (max)
Logic Low: 0 to 0.9 VDC
MeterView XL Software
Availability
Free download from
System
Requirements
Microsoft
®
Windows
®
7 & 10
Communicati
ons
USB 2.0 (Standard USB A to Micro USB B)
Cable provided
Configuration
Configure all parameters on the meter.
Configure meters one at a time.
Configuration
Files
Generate with or without meter connected;
Save to file for later use.
USB Power
Connection
Meter is powered by USB connection during
programming, if 4-20 mA loop is not
connected.
To download the latest MeterView XL programming
software and manual, visit