PD6928 Ex-Proof & I.S. Loop-Powered Flow Rate/Totalizer
Instruction Manual
68
Enabling or Disabling the
Backlight (
BACKLITE
)
The backlight may be enabled or disabled using the
System - Backlight menu. The backlight is enabled by
default, but the input must be wired appropriately for
the backlight to function. See
CapTouch Buttons Operation
Mode (
CAPTOUCH
)
CapTouch buttons have two modes of operation:
Normal and Delayed. Delayed mode prevents
accidental trigger of the buttons. In the Delayed
mode, the buttons enter into a low sensitivity state
(sleep) and they ignore quick button presses after 20
seconds of inactivity. To wake up the buttons, press
and hold any button for more than 2 seconds, the
buttons respond normally.
Viewing System Information
(
INFO
)
System information, such as software (firmware)
number and version, model number, and system tag,
may be viewed in the
INFO
menu. Press the
Right
Arrow
button to cycle through all available meter
information. Press
Menu
to go back to the previous
menu.
Calibrating the Internal mA
Reference (
ICAL
)
The meter is factory calibrated prior to shipment to display
0.00 to 100.00, which corresponds to the 4-20 mA input.
The calibration equipment is traceable to NIST standards.
The use of calibrated signal sources is necessary to
calibrate the internal source of the meter. The meter’s
internal source is what allows the user to scale the
meter without applying a signal.
Check calibration of the meter at least every
12 months.
Note:
Allow the meter to warm up for at least
15 minutes before performing the internal source
calibration procedure.
The
Internal Calibration
menu is part of the
Advanced
menu. Internal Calibration is performed as follows:
1. Press the
Menu
button to enter
Programming Mode
.
2. Press the
Up-Arrow
button
twice
and press
Enter
to access the
Advanced
menu.
3. Press the
Up-Arrow
button and press
Enter
to access the
System
menu.
4. Press the
Up-Arrow
button and press
Enter
to access the
ICAL
menu.
5. The meter displays
low
input current
message
(
4.000 mA
). Apply a 4 mA signal and press
Enter
. The display flashes for a moment
while the meter is accepting the low input
signal.
6.
After the display stops flashing, the display
moves to the
high
input calibration (
20.000
mA
). Apply the high input signal and press
Enter
. The display will flash again while the
meter is accepting the high input signal.