PD6800-0L1 Explosion-Proof Loop-Powered Process Meter
Instruction Manual
8
Cover Jam Screw
The cover jam screw should be properly installed
once the meter has been wired and tested in a safe
environment. The cover jam screw is intended to
prevent the removal of the meter cover in a flame-
proof environment without the use of tools. Using a
M2 hex wrench, turn the screw clockwise until the
screw contacts the meter. Turn the screw an
additional 1/4 to 1/2 turn to secure the cover.
Caution: Excess torque may damage the threads
and/or wrench.
Connections
To access the connectors, remove the enclosure cov-
er and unscrew the two captive screws that fasten the
display module. Disconnect the ribbon cable and re-
move the display module. Signal connections are
made to a four-terminal connector in the base of the
enclosure. Grounding connections are made to the
two ground screws provided on the base – one
internal and one external.
4-20 mA signal input positive
terminal connection
SIGNAL -
4-20 mA signal return/negative
terminal connection when not
using loop powered backlight.
BAC
+9-36 VDC when powering
backlight from external supply.
BACKLIGHT -
4-20 mA signal return/negative
terminal when using the
installed loop powered backlight
or ground/negative when power-
ing backlight from external
supply.
NPN open collector output
positive.
OUTPUT-
NPN open collector output
negative.
RESET +
Contact closure alarm
acknowledge, pull up to 3 VDC.
RESET-
Contact closure alarm
acknowledge ground/negative.
Refer to
•
Observe all safety regulations. Electrical wiring
should be performed in accordance with all
agency requirements and applicable national,
state, and local codes to prevent damage to the
meter and ensure personnel safety.
•
Static electricity can damage sensitive
components.
•
Observe safe handling precautions for
static-sensitive components.
•
Use proper grounding procedures/codes.
•
If the meter is installed in a high voltage
environment and a fault or installation error
occurs, high voltage may be present on any lead
or terminal.
Figure 3. Connector Board
SAFE-TOUCH
BUTTONS
BACKLIGHT
POWER
UNLOCK
LOCK
LOOP
9-36 VDC
+ - + -
SIGNAL
BACKLIGHT
+ - + -
OUTPUT
RESET